Inspections for the day of: Friday, June 7, 2019.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01907 Final6/6/20196/7/20196/7/2019 3:32:55 PMPNH
Side door is open, furnace is in the basement, please call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Lea Briggs
- vent termination ok
- no access to home can't let myself into home without homeowner. still need to check furnace connection
MEC19-01160 Final6/7/20196/7/20196/7/2019 3:22:39 PMPFAIL
Phone #: ###-#### Inspection requested via web by Lynn Johnston
- condensate line needs to extend into washer drain box
MEC19-01035 Final6/7/20196/7/20196/7/2019 3:21:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Lynn Johnston
- final ok
MEC19-01222 Rough-in6/7/20196/7/20196/7/2019 2:56:30 PMPPART
SOUT SIDE PART Phone #: ###-#### Inspection requested via web by Oleg Chervak
- south side duct work R/I ok
MEC19-02334 Rough-in6/7/20196/7/20196/7/2019 2:24:58 PMPFAIL
- condensate lines ok
- man J ok
-need to see 3 panasonic fans installed for drawing conditioned air to adjoining rooms
- inline fan for moving air from the second floor to the first floor
- electric heat source in master bathroom
MEC18-02531 Final6/6/20196/7/20196/7/2019 1:49:46 PMPPASS
Call Doug ahead of time ###-####
- bathroom exhaust fan
final ok
MEC19-01819 Final6/5/20196/7/20196/7/2019 1:19:31 PMPPASS
Please call Daniel in route to inspection ###-####
2- furnace ac coil co ok
MEC19-01738 Rough-in6/7/20196/7/20196/7/2019 1:04:46 PMPPASS
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
- R/I ok
MEC19-00898 Final6/6/20196/7/20196/7/2019 12:06:03 PMPPASS
AC: 1605 Phone #: ###-#### Inspection requested via web by Gary Reeves
- final ok
MEC19-01067 Final6/6/20196/7/20196/7/2019 12:04:13 PMPPASS
AC: 2105 Phone #: ###-#### Inspection requested via web by Gary Reeves
- final ok
MEC19-02334 Rough-in6/7/20196/7/20196/7/2019 11:39:07 AMPNR
CALL ME PLZ Phone #: ###-#### Inspection requested via web by Oleg Chervak
- condensate lines not ready
PLM19-01617 Plumbing Rough-in6/6/20196/7/20196/7/2019 11:19:24 AMAPART
if questions call Glen @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
1st floor stacks and under floor and kitchen area.................ds
MEC19-02358 Rough-in6/6/20196/7/20196/7/2019 11:05:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Frank Marturello
- need stamped Man J. onsite
- 5lb flue pressure test fail
MEC19-02358 Pressure Test6/6/20196/7/20196/7/2019 11:05:07 AMAFAIL
Phone #: ###-#### Inspection requested via web by Frank Marturello
- 5lb flue pressure test fail
- 20lb gas pressure test ok
- tagged meter location
MEC19-02346 Rough-in6/5/20196/7/20196/7/2019 10:00:39 AMAPASS
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
- duct seal ok
- R/I cover ok
- exhaust/ make up air has been deleted
- still need to check heater flues when installed insulation sheild ok
MEC19-02056 Pressure Test6/6/20196/7/20196/7/2019 9:30:15 AMAPASS
Pressure test for the gas line to the furnace. Also the flue vent will be under pressure. Phone #: ###-#### Inspection requested via web by Nicolas Barajas
- 5lb flue pressure test ok
- 20lb gas pressure test ok
- tagged meter location
MEC19-01022 Final6/6/20196/7/20196/7/2019 9:18:38 AMACANC
partial final on 120,121,123,229
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- reschedule as a R/I inspection for units 120,121,123,229
MEC19-01022 Rough-in6/7/20196/7/20196/7/2019 9:17:51 AMAPART
partial final on 120,121,123,229
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- units 120,121,123,229 R/I ok
MEC19-02336 Pressure Test6/7/20196/7/20196/7/2019 9:03:44 AMAPASS
Pressure gauge on outside in fenced area. Gate will be unlock after 8:30 Phone #: ###-#### Inspection requested via web by Bruce Lacy
- 20lb gas pressure test ok
MEC19-01141 Final6/6/20196/7/20196/7/2019 8:43:02 AMAPASS
Lock box code 2485
Box is on the electric meter in the back of the house. The house in not occupied only staged. Phone #: ###-#### Inspection requested via web by Tony Fogg
- final ok
MEC18-02700 Mec-Aging Inspection6/7/20196/7/20196/7/2019 8:04:12 AM FAIL
Need to make corrections and schedule inspection with homeowner.This permit has not been active since 7/10/2018. Permit will expire at next mechanical aging inspection if not active. Permit will have to be issued again having being expired.
MEC18-05201 Mec-Aging Inspection6/7/20196/7/20196/7/2019 7:58:42 AM FAIL
Need to schedule final inspection of fireplace with homeowner. R/I and gas pressure test pass in Oct 2018