PLM04-00642
| Final | 6/4/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | A | FAIL |
|
|
jeanette; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need to remove atmospheric type vacuum breaker and install spill-proof pressure type 6/8/2004 10:51:13 AM
|
PLM04-01472
| Water and/or Sewer | 6/7/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | A | PART |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes sewer line only -test ok ok to cover 6/8/2004 10:01:12 AM
|
PLM04-01522
| Water and/or Sewer | 6/7/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/7/2004 at 12:51:39 PM. Contact: ###-####.
|
PLM04-01048
| Final | 6/7/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | A | PART |
|
|
aaron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 6/8/2004 3:48:22 PM need to change grease trap to grease recover unit ( big-dipper ) as per Rick from bench sewer district oked temp 6/8/2004 3:58:22 PM
|
PLM04-01163
| Med/Gas Systems | 6/7/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | PART |
|
|
24 hour pressure test on med gas test ok need to provide labeling for med gas pipig as per N F P A 99C 6/8/2004 3:54:43 PM
|
PLM04-01201
| Final | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 6/8/2004 at 7:56:49 AM. Contact: ###-####. not ready 6/8/2004 1:37:50 PM
|
PLM04-01537
| Sprinkler (Final) | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | PASS |
|
|
###-####- steve
|
PLM03-03720
| Final | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/8/2004 at 9:56:52 AM. Contact: ###-####.
|
PLM04-01505
| Water and/or Sewer | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | PASS |
|
|
Roger; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
PLM04-00669
| Storm Drains | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | PART |
|
|
Don; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes need to finish storm drain lines and correct grade on storm drain lines talked to contractor will recall when ready 6/8/2004 1:13:52 PM
|
PLM04-00644
| Final | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | PART |
|
|
Kirk; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes need to install thermal expansion tank insall protective trap covers in new restroom sinks turn t&p drain line down on outside of building of new addition oked temp 6/8/2004 4:23:31 PM
|