BLD02-00648
| BLD-Aging Inspection | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | | PASS |
|
|
Talked to Dave Maxwell and he will schedule for 6/11. 6/10/2004 1:06:10 PM
|
BLD04-00901
| FIRE-Final Inspection | 6/7/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/7/2004 at 11:44:28 AM. Contact: ###-####.
|
MIS04-00093
| FIR-Final | 6/7/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | A | PASS |
|
|
Jeff, ###-#### or Roy - ###-#### - please let cathy know when final
|
FIR04-00174
| INSP-Sprinkler Rough-in/Hydro | 6/7/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | A | FAIL |
|
|
###-#### mike See plans for areas that need corections: heads overspaced; straps and hangers; need standard response head in elevator machine room; need 286 heads within 7 ft of unot heaters; overspaced at "future stair" on west side of building 6/8/2004 10:15:24 AM
|
FIR04-00010
| INSP-Final Inspection | 6/3/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | FAIL |
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Sprinkler bell not working; address wrong for dispatching from monitoring company; duct detectors relay not latching 6/8/2004 3:52:12 PM
|
FIR04-00147
| INSP-Final Inspection | 6/8/2004 | 6/8/2004 | 6/8/2004 12:00:00 AM | P | FAIL |
|
|
Billy; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes activation of extinguishing system doesn't generate alarm notification; dialer on alarm panel not working - to be fixed by 6/11/04; correction notice left with Billy and he is going to give to manager 6/8/2004 3:57:21 PM
|
BLD04-00675
| FIRE-Final Inspection | 6/7/2004 | 6/8/2004 | 6/7/2004 12:00:00 AM | A | PASS |
|
|
carl; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|