FIR06-00283
| INSP-Final Inspection | 6/8/2006 | 6/8/2006 | 6/12/2006 10:14:21 AM | P | PASS |
|
|
Permit finaled.
|
FIR06-00308
| INSP-Alarm Testing | 6/7/2006 | 6/8/2006 | 6/8/2006 3:05:36 PM | P | PASS |
|
|
Fire alarm field inspection is satisfactory.
|
FIR06-00305
| INSP-Final Inspection | 6/8/2006 | 6/8/2006 | 6/8/2006 3:04:50 PM | P | PASS |
|
|
The correct sample tubes have been installed, inspection passed.
|
FIR06-00382
| INSP-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 1:41:51 PM | P | FAIL |
|
|
Pull stations at three locations exceed the maximum height AFF.
|
BLD06-00759
| FIRE-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 1:40:19 PM | A | NR |
|
|
The project related fire alarm must be finaled prior to building life safety final approval.
|
BLD05-00624
| FIRE-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 1:08:24 PM | A | DEFR |
|
|
Inspection to be completed 6/9
|
BLD06-00213
| FIRE-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 12:37:35 PM | A | FAIL |
|
|
Project related fire sprinkler permit is not yet finaled, mechanical issues with respect to duct detectors are not resolved.
|
FIR06-00296
| INSP-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 12:24:09 PM | A | FAIL |
|
|
The existing building fire sprinkler system is not yet current with an annual inspection, ceiling tile is missing at several locations, some escutcheons are still missing.
|
FIR05-00764
| INSP-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 10:43:48 AM | A | FAIL |
|
|
Manual pull stations at several locations are installed above max. height allowed, one H/S is overspaced in the open office area, remote indicator for the duct detector in the computer room is non-functional, fire alarm wire at some locations is incorrectly attatched, need to test one duct detector above a confrence room. FACP, nac panel, batteries, phone lines tested okay. Still need to test a/v's, manual pulls, dB, verify signals, etc.
|
FIR06-00180
| INSP-Sprinkler Rough-in/Hydro | 6/7/2006 | 6/8/2006 | 6/8/2006 8:48:28 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: David Uli Inspection cancelled from web by: David Uli
|