Inspections for the day of: Thursday, June 8, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00283 INSP-Final Inspection6/8/20066/8/20066/12/2006 10:14:21 AMPPASS
Permit finaled.
FIR06-00308 INSP-Alarm Testing6/7/20066/8/20066/8/2006 3:05:36 PMPPASS
Fire alarm field inspection is satisfactory.
FIR06-00305 INSP-Final Inspection6/8/20066/8/20066/8/2006 3:04:50 PMPPASS
The correct sample tubes have been installed, inspection passed.
FIR06-00382 INSP-Final Inspection6/7/20066/8/20066/8/2006 1:41:51 PMPFAIL
Pull stations at three locations exceed the maximum height AFF.
BLD06-00759 FIRE-Final Inspection6/7/20066/8/20066/8/2006 1:40:19 PMANR
The project related fire alarm must be finaled prior to building life safety final approval.
BLD05-00624 FIRE-Final Inspection6/7/20066/8/20066/8/2006 1:08:24 PMADEFR
Inspection to be completed 6/9
BLD06-00213 FIRE-Final Inspection6/7/20066/8/20066/8/2006 12:37:35 PMAFAIL
Project related fire sprinkler permit is not yet finaled, mechanical issues with respect to duct detectors are not resolved.
FIR06-00296 INSP-Final Inspection6/7/20066/8/20066/8/2006 12:24:09 PMAFAIL
The existing building fire sprinkler system is not yet current with an annual inspection, ceiling tile is missing at several locations, some escutcheons are still missing.
FIR05-00764 INSP-Final Inspection6/7/20066/8/20066/8/2006 10:43:48 AMAFAIL
Manual pull stations at several locations are installed above max. height allowed, one H/S is overspaced in the open office area, remote indicator for the duct detector in the computer room is non-functional, fire alarm wire at some locations is incorrectly attatched, need to test one duct detector above a confrence room. FACP, nac panel, batteries, phone lines tested okay. Still need to test a/v's, manual pulls, dB, verify signals, etc.
FIR06-00180 INSP-Sprinkler Rough-in/Hydro6/7/20066/8/20066/8/2006 8:48:28 AMPCANC
Phone #: ###-#### Internet Inspection Request from: David Uli Inspection cancelled from web by: David Uli