FIR06-00291
| INSP-Sprinkler Rough-in/Hydro | 6/8/2006 | 6/8/2006 | 6/8/2006 5:44:27 PM | P | PASS |
|
|
Sprinkler piping is ok to cover. One upright sprinkler head has been painted and needs replacing.
|
FIR06-00068
| INSP-Sprinkler Rough-in | 6/8/2006 | 6/8/2006 | 6/8/2006 3:05:21 PM | P | PASS |
|
|
The remaining overhead sprinkler piping is ok for rough-in and the ceiling tile in the office area can be installed. Two heads in the spiral freezer are too close but per the contractor a wall is to be installed between the two. This will need to be verified at the final or next inspection.
|
MIS06-00113
| FIR-Final | 6/8/2006 | 6/8/2006 | 6/8/2006 3:03:33 PM | P | FAIL |
|
|
Provide signage at the emergency shutoff switch for the gas pumps and provide exit signs at the two exit doors.
|
FIR06-00180
| INSP-Alarm Testing | 6/8/2006 | 6/8/2006 | 6/8/2006 3:02:43 PM | P | FAIL |
|
|
Duct smoke detectors are mounted on angles and near 90's. Provide differential pressure readings to verify they work. Provide some means of resetting the duct smoke detectors other than accessing above the ceiling such as a breaker, key or panel reset. The descriptors for the contact ID points at the monitoring station had not been set up yet. Need to retest devices to reverify points.
|
FIR06-00212
| INSP-Sprinkler Rough-in/Hydro | 6/8/2006 | 6/8/2006 | 6/8/2006 1:25:09 PM | A | FAIL |
|
|
No city approved plans on site for the fire sprinkler inspection.
|
BLD06-00596
| FIRE-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 1:12:30 PM | A | PASS |
|
|
Life safety finaled
|
MIS06-00111
| FIR-Final | 6/7/2006 | 6/8/2006 | 6/8/2006 11:37:16 AM | A | PASS |
|
|
fire life safety finaled
|
BLD05-02094
| FIRE-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 8:32:43 AM | A | PASS |
|
|
Life safety finaled. The duct smoke detectors have been removed since they are not required by code.
|
BLD05-02092
| FIRE-Final Inspection | 6/7/2006 | 6/8/2006 | 6/8/2006 8:31:59 AM | A | PASS |
|
|
Life safety finaled
|
MIS06-00136
| FIR-Final | 6/7/2006 | 6/8/2006 | 6/7/2006 10:34:29 AM | A | CANC |
|
|
alicia ###-#### Inspection cancelled from web by: Marsha Smylie
|