Inspections for the day of: Thursday, June 8, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00291 INSP-Sprinkler Rough-in/Hydro6/8/20066/8/20066/8/2006 5:44:27 PMPPASS
Sprinkler piping is ok to cover. One upright sprinkler head has been painted and needs replacing.
FIR06-00068 INSP-Sprinkler Rough-in6/8/20066/8/20066/8/2006 3:05:21 PMPPASS
The remaining overhead sprinkler piping is ok for rough-in and the ceiling tile in the office area can be installed. Two heads in the spiral freezer are too close but per the contractor a wall is to be installed between the two. This will need to be verified at the final or next inspection.
MIS06-00113 FIR-Final6/8/20066/8/20066/8/2006 3:03:33 PMPFAIL
Provide signage at the emergency shutoff switch for the gas pumps and provide exit signs at the two exit doors.
FIR06-00180 INSP-Alarm Testing6/8/20066/8/20066/8/2006 3:02:43 PMPFAIL
Duct smoke detectors are mounted on angles and near 90's. Provide differential pressure readings to verify they work. Provide some means of resetting the duct smoke detectors other than accessing above the ceiling such as a breaker, key or panel reset. The descriptors for the contact ID points at the monitoring station had not been set up yet. Need to retest devices to reverify points.
FIR06-00212 INSP-Sprinkler Rough-in/Hydro6/8/20066/8/20066/8/2006 1:25:09 PMAFAIL
No city approved plans on site for the fire sprinkler inspection.
BLD06-00596 FIRE-Final Inspection6/7/20066/8/20066/8/2006 1:12:30 PMAPASS
Life safety finaled
MIS06-00111 FIR-Final6/7/20066/8/20066/8/2006 11:37:16 AMAPASS
fire life safety finaled
BLD05-02094 FIRE-Final Inspection6/7/20066/8/20066/8/2006 8:32:43 AMAPASS
Life safety finaled. The duct smoke detectors have been removed since they are not required by code.
BLD05-02092 FIRE-Final Inspection6/7/20066/8/20066/8/2006 8:31:59 AMAPASS
Life safety finaled
MIS06-00136 FIR-Final6/7/20066/8/20066/7/2006 10:34:29 AMACANC
alicia ###-#### Inspection cancelled from web by: Marsha Smylie