Inspections for the day of: Friday, June 8, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00463 INSP-Final Inspection6/8/20076/8/20076/11/2007 7:12:51 AMPCANC
Forrest, Please let me know as soon as possible when you think you can make it out to this project. I need to make arrangements with the building owner, and the sprinkler contractor to be there as well. Thanks. Jason ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
FIR07-00230 INSP-Final Inspection6/7/20076/8/20076/8/2007 2:55:42 PMPPART
Trip and alarm testing completed satisfactory, overhead install is acceptable. Items needed for final include the required 24 hr. air test per NFPA 13 and a passable UG hydrostatic test.
FIR07-00428 INSP-Final Inspection6/7/20076/8/20076/8/2007 2:52:11 PMAPASS
Fire alarm work completed and tested satisfactory, permit finaled.
BLD07-01071 FIRE-Final Inspection6/8/20076/8/20076/8/2007 1:56:36 PMPFAIL
Need to provide approved hardware at three locations, a fire sprinkler permit will be required to make necessary corrections caused by building modifications, also noted two fire alarm notification devices have been relocated without a permit and will need to be tested and inspected with the proper permit prior to fire life safety final, also need to repair balasts on two emergency lights.
FIR07-00287 INSP-Final Inspection6/8/20076/8/20076/8/2007 1:04:27 PMPPASS
Fire sprinkler modifications are acceptable, permit finaled.
FIR07-00290 INSP-Final Inspection6/8/20076/8/20076/8/2007 1:03:29 PMPPASS
Fire sprinkler permit finaled.
FIR07-00291 INSP-Final Inspection6/8/20076/8/20076/8/2007 1:02:33 PMPPASS
Fire sprinkler work passed inspection, permit finaled.
FIR06-00948 INSP-Final Inspection6/6/20076/8/20076/8/2007 11:56:40 AMANH
No access provided to complete final inspection as scheduled.
FIR07-00230 INSP-Sprinkler Rough-in/Hydro6/7/20076/8/20076/8/2007 11:55:49 AMAFAIL
UG hydrostatic test failed due to pressure loss at the guage of 15 psi. over a two hour period.
FIR06-00504 INSP-Sprinkler Rough-in6/7/20076/8/20076/8/2007 10:04:39 AMACANC
rough in for 2nd - 6th floors Jonathon is the contact Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
FIR07-00193 INSP-Sprinkler Rough-in/Hydro6/5/20076/8/20076/8/2007 7:41:06 AMACANC
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
FIR07-00424 INSP-Final Inspection6/7/20076/8/20076/7/2007 2:15:32 PMAPASS
Inspection completed on 6/7. Fire sprinkler work is acceptable, inspection passed, permit finaled.