FIR07-00463
| INSP-Final Inspection | 6/8/2007 | 6/8/2007 | 6/11/2007 7:12:51 AM | P | CANC |
|
|
Forrest, Please let me know as soon as possible when you think you can make it out to this project. I need to make arrangements with the building owner, and the sprinkler contractor to be there as well. Thanks. Jason ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
FIR07-00230
| INSP-Final Inspection | 6/7/2007 | 6/8/2007 | 6/8/2007 2:55:42 PM | P | PART |
|
|
Trip and alarm testing completed satisfactory, overhead install is acceptable. Items needed for final include the required 24 hr. air test per NFPA 13 and a passable UG hydrostatic test.
|
FIR07-00428
| INSP-Final Inspection | 6/7/2007 | 6/8/2007 | 6/8/2007 2:52:11 PM | A | PASS |
|
|
Fire alarm work completed and tested satisfactory, permit finaled.
|
BLD07-01071
| FIRE-Final Inspection | 6/8/2007 | 6/8/2007 | 6/8/2007 1:56:36 PM | P | FAIL |
|
|
Need to provide approved hardware at three locations, a fire sprinkler permit will be required to make necessary corrections caused by building modifications, also noted two fire alarm notification devices have been relocated without a permit and will need to be tested and inspected with the proper permit prior to fire life safety final, also need to repair balasts on two emergency lights.
|
FIR07-00287
| INSP-Final Inspection | 6/8/2007 | 6/8/2007 | 6/8/2007 1:04:27 PM | P | PASS |
|
|
Fire sprinkler modifications are acceptable, permit finaled.
|
FIR07-00290
| INSP-Final Inspection | 6/8/2007 | 6/8/2007 | 6/8/2007 1:03:29 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00291
| INSP-Final Inspection | 6/8/2007 | 6/8/2007 | 6/8/2007 1:02:33 PM | P | PASS |
|
|
Fire sprinkler work passed inspection, permit finaled.
|
FIR06-00948
| INSP-Final Inspection | 6/6/2007 | 6/8/2007 | 6/8/2007 11:56:40 AM | A | NH |
|
|
No access provided to complete final inspection as scheduled.
|
FIR07-00230
| INSP-Sprinkler Rough-in/Hydro | 6/7/2007 | 6/8/2007 | 6/8/2007 11:55:49 AM | A | FAIL |
|
|
UG hydrostatic test failed due to pressure loss at the guage of 15 psi. over a two hour period.
|
FIR06-00504
| INSP-Sprinkler Rough-in | 6/7/2007 | 6/8/2007 | 6/8/2007 10:04:39 AM | A | CANC |
|
|
rough in for 2nd - 6th floors Jonathon is the contact Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR07-00193
| INSP-Sprinkler Rough-in/Hydro | 6/5/2007 | 6/8/2007 | 6/8/2007 7:41:06 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
|
FIR07-00424
| INSP-Final Inspection | 6/7/2007 | 6/8/2007 | 6/7/2007 2:15:32 PM | A | PASS |
|
|
Inspection completed on 6/7. Fire sprinkler work is acceptable, inspection passed, permit finaled.
|