FIR06-00015
| INSP-Conference | 6/4/2010 | 6/8/2010 | 6/8/2010 3:51:18 PM | A | DONE |
|
|
Per James he is still trying to get with Mike. Follow up inspection has been set up in two weeks.
|
FIR06-00062
| INSP-Conference | 6/4/2010 | 6/8/2010 | 6/8/2010 3:50:53 PM | A | DONE |
|
|
Per James he is still trying to get with Mike. Follow up inspection has been set up in two weeks.
|
FIR05-00021
| INSP-Conference | 6/4/2010 | 6/8/2010 | 6/8/2010 3:50:27 PM | A | DONE |
|
|
Per James he is still trying to get with Mike. Follow up inspection has been set up in two weeks.
|
FIR10-00039
| INSP-Conference | 6/4/2010 | 6/8/2010 | 6/8/2010 3:50:02 PM | A | DONE |
|
|
Per James he is still trying to get with Mike. Follow up inspection has been set up in two weeks.
|
FIR10-00036
| INSP-Conference | 6/4/2010 | 6/8/2010 | 6/8/2010 3:49:38 PM | A | DONE |
|
|
Per James he is still trying to get with Mike. Follow up inspection has been set up in two weeks.
|
BLD10-01049
| FIRE-Final Inspection | 6/8/2010 | 6/8/2010 | 6/8/2010 3:45:19 PM | P | FAIL |
|
|
Provide single action hardware for office door 112, provide a tagged and mounted fire extinguisher for the basement area and provide a current inspection tag for the fire extinguisher on the main level.
|
BLD09-00323
| FIRE-Conference | 6/7/2010 | 6/8/2010 | 6/8/2010 3:40:38 PM | A | DONE |
|
|
I went over live safety requirements which included a knox box, manual locks on the interior doors, fire extinguishers and exit signs/emergency lights.
|
FIR09-00728
| INSP-Final Inspection | 6/7/2010 | 6/8/2010 | 6/8/2010 2:39:36 PM | P | PASS |
|
|
Permit finaled.
|
FIR10-00147
| INSP-Sprinkler Rough-in | 6/7/2010 | 6/8/2010 | 6/8/2010 1:07:59 PM | A | CANC |
|
|
The fire sprinkler plans have been resubmitted and are in the review status. I let rick know I would do the inspection when the new plans had been re-issued.
|
BLD10-00814
| FIRE-Final Inspection | 6/7/2010 | 6/8/2010 | 6/8/2010 11:48:21 AM | A | FAIL |
|
|
Repair the insulation at the roof deck since it is obstructing the upright sprinkler protection, repair the emergency light in the warehouse area and provide a fire extinguisher in the mezzanine.
|
BLD10-00691
| FIRE-Final Inspection | 6/7/2010 | 6/8/2010 | 6/8/2010 10:43:27 AM | A | FAIL |
|
|
Provide signage on the door into the UPS room and on the outside and inside of the electrical equipment/batterys as per the approved plans/notes. Also smoke detection is required in the UPS room as per the approved plans/notes.
|
FIR10-00234
| INSP-Final Inspection | 6/4/2010 | 6/8/2010 | 6/8/2010 10:41:54 AM | A | PASS |
|
|
Permit finaled
|
BLD10-00196
| FIRE-Final Inspection | 6/7/2010 | 6/8/2010 | 6/8/2010 10:19:20 AM | A | PASS |
|
|
Life safety passed.
|
BLD10-00198
| FIRE-Final Inspection | 6/7/2010 | 6/8/2010 | 6/8/2010 10:17:18 AM | A | PASS |
|
|
Life safety passed.
|
FIR10-00133
| INSP-Final Inspection | 6/7/2010 | 6/8/2010 | 6/8/2010 10:16:11 AM | A | PASS |
|
|
Permit finaled
|
FIR10-00226
| INSP-Final Inspection | 6/1/2010 | 6/8/2010 | 6/8/2010 10:03:05 AM | A | PASS |
|
|
Permit finaled. Netcon was 5.
|
FIR10-00227
| INSP-Final Inspection | 6/1/2010 | 6/8/2010 | 6/8/2010 10:02:24 AM | A | PASS |
|
|
Permit finaled. Netcon was 5.
|
FIR07-01003
| INSP-Sprinkler Rough-in | 6/7/2010 | 6/8/2010 | 6/8/2010 10:01:30 AM | A | PASS |
|
|
The sprinkler piping is ok to cover.
|