MIS15-00125
| ELE-Conference | 6/5/2015 | 6/8/2015 | 6/8/2015 4:20:12 PM | P | FAIL |
|
|
Work done without permits - contact homeowner Lester Phone #: ###-#### 210-11 (c) 3 bath outlets shall be a dedicated 20 amp circuit 210.8- All bathroom receptacles shall have GFCI protection. Section 4-05-18 ELECTRICAL PERMIT REQUIRED Before any person installs or alters any electrical wiring, equipment, apparatus or fixture, they shall file a permit application with the Electrical Section. Exception: Emergency Work. If immediate alteration or installation of electrical wiring, equipment, apparatus or fixtures is necessary for reasons of public safety and/or welfare and an electrical permit cannot first be obtained without further endangering the public safety and/or welfare, such alteration or installation may be made without first obtaining the electrical permit therefore but the required electrical permit shall be obtained during the next business day after such alteration or installation shall have been made.
|
MIS15-00125
| ELE-Conference | 6/8/2015 | 6/8/2015 | 6/8/2015 4:01:58 PM | P | FAIL |
|
|
Work done without permits - contact homeowner Lester Phone #: ###-#### 334-30 nm cable shall be supported with 12 in of a box 300.4 nm cable ran through bored holes shall maintain 1 1/4 from face of surface to protect from physical damage 300.5 (h) nm xcable shall enter boxes through busshed openings 110-14 electrical terminations shall be considered to be in a enclosure
|
ELE15-01094
| Final | 6/8/2015 | 6/8/2015 | 6/8/2015 2:55:44 PM | P | PASS |
|
|
Please call 30 mins prior to insp to gain access Phone #: ###-#### Inspection requested via web by Eric Brown Final ok
|
ELE15-01669
| Temporary Service | 6/5/2015 | 6/8/2015 | 6/8/2015 1:58:41 PM | P | PASS |
|
|
Ryan is the contact at ###-#### Over head temp pole to access the property the gate east of the temp pole is unlocked. Phone #: ###-#### Inspection requested via web by Tracy Robertson t/s o/h n ok
|
ELE15-01113
| Final | 6/5/2015 | 6/8/2015 | 6/8/2015 1:58:28 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears Final ok
|
ELE15-01285
| Electrical Rough-In | 6/8/2015 | 6/8/2015 | 6/8/2015 10:22:04 AM | A | PASS |
|
|
underground 2 inch conduits for the sub panels Phone #: ###-#### Inspection requested via web by Karl Paige Underground from transformer to each tenant space rough in ok cover
|
ELE15-01543
| Rough-In Permanent Service | 6/5/2015 | 6/8/2015 | 6/8/2015 9:58:00 AM | A | PASS |
|
|
Cody is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
|
ELE15-00601
| Electrical Rough-In | 6/5/2015 | 6/8/2015 | 6/8/2015 9:35:10 AM | A | PASS |
|
|
Ceiling inspection please Phone #: ###-#### Inspection requested via web by Celinda Winters Grid rough in ok cover
|
ELE15-01656
| Conference | 6/3/2015 | 6/8/2015 | 6/8/2015 9:22:37 AM | A | DONE |
|
|
Jeffwould like as early as possible but could you please call with an approx meet time Phone #: ###-#### Discussed code requirements for kitchen remodel. Owner may locate some receptacles serving counter top below or on face of cab due to handicap individual living at residence. Min circuits for counter top, ratings of appl. determine whether dedicated or not.
|
ELE15-01687
| Permanent Service | 6/5/2015 | 6/8/2015 | 6/8/2015 8:42:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl p/s o/h rec ok
|
ELE15-01687
| Final | 6/8/2015 | 6/8/2015 | 6/8/2015 8:42:19 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl Service reconnect Final ok
|
ELE11-02817
| ELE-Aging Inspection | 6/8/2015 | 6/8/2015 | 6/8/2015 6:35:14 AM | | DONE |
|
|
Waiting on contractor
|