Inspections for the day of: Monday, June 8, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00330 INSP-Alarm Testing6/8/20156/8/20156/8/2015 4:15:21 PMPPART
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate.
NOTE: No FSDs or elevator functions tested this visit.
FIR14-00727 INSP-Alarm Testing6/8/20156/8/20156/8/2015 4:13:32 PMPPART
Inspection/ test of fire alarm system for the permit coverage area, except common area of Bldg D., including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate.
NOTE: No FSDs or elevator functions tested this visit.
FIR14-00729 INSP-Alarm Testing6/8/20156/8/20156/8/2015 4:11:53 PMPPART
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate.
NOTE: No FSDs or elevator functions tested this visit.
FIR14-00271 INSP-Alarm Testing6/8/20156/8/20156/8/2015 4:10:30 PMPPART
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing.
NOTE: No FSDs or elevator functions tested this visit.
FIR14-00362 INSP-Final Inspection6/5/20156/8/20156/8/2015 4:06:40 PMPPART
Inspection of fire alarm system interface, including water flows of system risers, tamper devices, control valves, etc. Waterflows came in at approx. 30-40 seconds.All pump room tampers tested OK. All device addresses appeared accurate.
FIR14-00681 INSP-Sprinkler Rough-in/Hydro6/5/20156/8/20156/8/2015 4:04:31 PMPPART
Inspection of fire alarm system interface, including water flows of system risers, tamper devices, control valves, etc. Waterflows came in at approx. 30-40 seconds. All device addresses appeared accurate.
FIR14-00344 INSP-Final Inspection6/5/20156/8/20156/8/2015 4:01:17 PMPPART
Inspection of fire alarm interface, including water flows, tamper supervisory devices, pump activations, etc., also exterior bell activation. All W/F tested OK (within 90 seconds - mostly around 30-40 seconds).
All addresses appeared OK
FIR14-00792 INSP-Sprinkler Rough-in6/5/20156/8/20156/8/2015 11:43:38 AMAPART
Hard lid rough inspection for Bldg. H wet pipe system - see plans for areas inspected.
OK to cover these areas.
FIR14-00815 INSP-Sprinkler Rough-in6/6/20156/8/20156/8/2015 9:50:49 AMAPART
Rough to cover inspection for east side of clubhouse wet system. OK to Cover.
NOTE: Proper coverage of garage type door on east wall - opening to pool, will be checked after door is installed.