FIR14-00330
| INSP-Alarm Testing | 6/8/2015 | 6/8/2015 | 6/8/2015 4:15:21 PM | P | PART |
|
|
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate. NOTE: No FSDs or elevator functions tested this visit.
|
FIR14-00727
| INSP-Alarm Testing | 6/8/2015 | 6/8/2015 | 6/8/2015 4:13:32 PM | P | PART |
|
|
Inspection/ test of fire alarm system for the permit coverage area, except common area of Bldg D., including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate. NOTE: No FSDs or elevator functions tested this visit.
|
FIR14-00729
| INSP-Alarm Testing | 6/8/2015 | 6/8/2015 | 6/8/2015 4:11:53 PM | P | PART |
|
|
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate. NOTE: No FSDs or elevator functions tested this visit.
|
FIR14-00271
| INSP-Alarm Testing | 6/8/2015 | 6/8/2015 | 6/8/2015 4:10:30 PM | P | PART |
|
|
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. NOTE: No FSDs or elevator functions tested this visit.
|
FIR14-00362
| INSP-Final Inspection | 6/5/2015 | 6/8/2015 | 6/8/2015 4:06:40 PM | P | PART |
|
|
Inspection of fire alarm system interface, including water flows of system risers, tamper devices, control valves, etc. Waterflows came in at approx. 30-40 seconds.All pump room tampers tested OK. All device addresses appeared accurate.
|
FIR14-00681
| INSP-Sprinkler Rough-in/Hydro | 6/5/2015 | 6/8/2015 | 6/8/2015 4:04:31 PM | P | PART |
|
|
Inspection of fire alarm system interface, including water flows of system risers, tamper devices, control valves, etc. Waterflows came in at approx. 30-40 seconds. All device addresses appeared accurate.
|
FIR14-00344
| INSP-Final Inspection | 6/5/2015 | 6/8/2015 | 6/8/2015 4:01:17 PM | P | PART |
|
|
Inspection of fire alarm interface, including water flows, tamper supervisory devices, pump activations, etc., also exterior bell activation. All W/F tested OK (within 90 seconds - mostly around 30-40 seconds). All addresses appeared OK
|
FIR14-00792
| INSP-Sprinkler Rough-in | 6/5/2015 | 6/8/2015 | 6/8/2015 11:43:38 AM | A | PART |
|
|
Hard lid rough inspection for Bldg. H wet pipe system - see plans for areas inspected. OK to cover these areas.
|
FIR14-00815
| INSP-Sprinkler Rough-in | 6/6/2015 | 6/8/2015 | 6/8/2015 9:50:49 AM | A | PART |
|
|
Rough to cover inspection for east side of clubhouse wet system. OK to Cover. NOTE: Proper coverage of garage type door on east wall - opening to pool, will be checked after door is installed.
|