Inspections for the day of: Wednesday, June 8, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00152 INSP-Sprinkler Rough-in6/8/20166/8/20166/8/2016 2:49:12 PMPPASS
See the city approved plans for locations marked "ok" where piping is ok to cover.
BLD16-01968 FIRE-Final Inspection6/6/20166/8/20166/8/2016 2:48:23 PMACANC
Timothy was not able to meet me when I was available.
FIR16-00332 INSP-Final Inspection6/8/20166/8/20166/8/2016 11:05:39 AMPPASS
Permit finaled
FIR16-00131 INSP-Sprinkler Rough-in/Hydro6/7/20166/8/20166/8/2016 10:58:38 AMAPASS
The overhead hydros for Foam Gen. System, Wet Hanger, Hose System and the Test Header side of the Pump Room piping passed inspection.
FIR15-00709 INSP-Sprinkler Rough-in6/7/20166/8/20166/8/2016 10:56:39 AMAPASS
The piping above the second and third floor hardlid at the west stairs is ok to cover and the second floor elevator lobby piping is ok to cover.
FIR15-00822 INSP-Final Inspection6/8/20166/8/20166/8/2016 6:56:22 AMAPART
Per the Fire Marshal, a TCO can be issued for the building permit (BLD15-01869) for the next 30 days. The static pressure at the base of the fire riser will need to be monitored and recorded over the next 30 days by the general contractor. These readings will be evaluated by the Fire Marshal at the end of the 30 days to determine if fire sprinkler system design changes will be necessary under (FIR15-00822) to accommodate the actual water supply available onsite.
BLD15-01869 BLD-Final6/8/20166/8/20166/8/2016 6:55:47 AMAPART
Per the Fire Marshal, a TCO can be issued for the building permit (BLD15-01869) for the next 30 days. The static pressure at the base of the fire riser will need to be monitored and recorded over the next 30 days by the general contractor. These readings will be evaluated by the Fire Marshal at the end of the 30 days to determine if fire sprinkler system design changes will be necessary under (FIR15-00822) to accommodate the actual water supply available onsite.