Inspections for the day of: Thursday, June 8, 2017.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01780 Permanent Service6/8/20176/8/20176/8/2017 1:35:14 PMPPASS
***MUST CALL Darrin burell for access. call before arrival so he can meet you there Phone #: ###-#### Inspection requested via web by mike brown
p/s u/g rec ok
ELE17-01780 Final6/8/20176/8/20176/8/2017 1:30:16 PMPPASS
***MUST CALL Darrin burell for access. call before arrival so he can meet you there Phone #: ###-#### Inspection requested via web by mike brown Final ok
ELE17-01779 Permanent Service6/8/20176/8/20176/8/2017 1:29:51 PMPPASS
*** MUST CALL Darin Burrell for access prior to arrival so he can meet you on site!! Phone #: ###-#### Inspection requested via web by mike brown
p/s u/g rec ok
ELE17-01779 Final6/8/20176/8/20176/8/2017 1:29:51 PMPPASS
*** MUST CALL Darin Burrell for access prior to arrival so he can meet you on site!! Phone #: ###-#### Inspection requested via web by mike brown
final ok
ELE16-01667 Final6/8/20176/8/20176/8/2017 11:46:44 AMAFAIL
Just units 301,302,303,304,402,403,404 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
4-05-24 Inspection required on all floor heat installions.
210.52(B)- Kitchen counter top areas shall have a receptacle outlet with 24" of edge of counter. counter off dining area 1 receptacle on left of 48" counter top.
250.140- Dryers in units shall have grounded and grounding terminations seperated. In cord junction 2 white grounded present, 1 terminated with neutral and 1 with ground.
410.16(C)- Closet luminaires, for recessed 6" minimum clearance from storage shelf, for surface LED 12" clearance required. Several unit too close.
422.11(A)- Water heaters shall be fused to manufacturers specs. 60 amp installed on 25 amp recommended fusing.
422.30- A disconnecting means shall be provided to disconnect ungrounded from appliances. Water heaters and range hoods.
Unit 403 deck receptacle not trimmed.
ELE17-01627 Electrical Rough-In6/6/20176/8/20176/8/2017 9:53:36 AMAPASS
Rough in walls only no ceilings Phone #: ###-#### Inspection requested via web by Cathy Duchek
Walls only rough in ok cover
ELE16-03931 Electrical Rough-In6/7/20176/8/20176/8/2017 9:53:01 AMAPASS
unit 704, unit 722 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Noted in office, units noted rough in ok cover
ELE16-03932 Electrical Rough-In6/7/20176/8/20176/8/2017 9:52:26 AMAPASS
unit 724 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Noted in office, unit noted rough in ok cover
ELE17-01301 Permanent Service6/5/20176/8/20176/8/2017 8:46:17 AMACANC
Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden duplicate request
ELE17-01297 Permanent Service6/5/20176/8/20176/8/2017 8:45:54 AMACANC
Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden Duplicate request
ELE17-01299 Permanent Service6/5/20176/8/20176/8/2017 8:45:34 AMACANC
Contact Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden Duplicate request
ELE17-01285 Permanent Service6/6/20176/8/20176/8/2017 8:45:16 AMACANC
Paul Wheeler
Phone #: ###-#### Inspection requested via web by Deb Gooden Duplicate request
ELE17-01284 Permanent Service6/5/20176/8/20176/8/2017 8:44:56 AMACANC
Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden Duplicate request
ELE17-01291 Permanent Service6/5/20176/8/20176/8/2017 8:43:53 AMAFAIL
Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.9- Equipment intended to interupt current at fault levels shall have an interupting rating at nominal circuit voltage at least equal to the current available at the line terminals of the equipment. 16,448 available and 10k rated equipment installed.
ELE17-01292 Permanent Service6/6/20176/8/20176/8/2017 8:43:19 AMAFAIL
Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden
110.9- Equipment intended to interupt current at fault levels shall have an interupting rating at nominal circuit voltage at least equal to the current available at the line terminals of the equipment. 16,448 available and 10k rated equipment installed.