Inspections for the day of: Friday, June 8, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00094 INSP-Sprinkler Rough-in6/7/20186/8/20186/8/2018 11:48:29 AMPCANC
Per Rand this will be rescheduled for monday or tuesday.

Rand Phone #: ###-####
BLD17-00747 FIRE-Final Inspection6/8/20186/8/20186/8/2018 11:34:11 AMPCANC
To be rescheduled per Jade until he can get pland and small documents on site.

Jade Conrad Phone #: ###-####
FIR18-00045 INSP-Final Inspection6/7/20186/8/20186/8/2018 11:28:40 AMAFAIL
We tested the duct smoke detector for shutdown and it functioned but the issue is per Potter tech support this duct detector, DDA, is not for outdoor use. A different detector listed for outdoor use, maybe with an enclosure, is going to need to be submitted/approved/installed and tested.

Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR17-00198 INSP-Sprinkler Rough-in/Hydro6/7/20186/8/20186/8/2018 9:18:36 AMAPASS
2nd,3rd floor hydro tests passed.
BLD18-01586 FIRE-Final Inspection6/7/20186/8/20186/8/2018 8:47:29 AMAPASS
Life safety passed

SId Phone #: ###-####
FIR18-00438 INSP-Final Inspection6/7/20186/8/20186/8/2018 8:43:31 AMAPASS
permit finaled

Tom Phone #: ###-####
FIR18-00399 INSP-Final Inspection6/7/20186/8/20186/8/2018 8:14:17 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-00665 FIRE-Final Inspection6/7/20186/8/20186/8/2018 12:00:00 AMPCANC
Mark Phone #: ###-####
FIR18-00129 INSP-Final Inspection6/7/20186/8/20186/7/2018 3:21:06 PMAPASS
Permit finaled