FIR18-00094
| INSP-Sprinkler Rough-in | 6/7/2018 | 6/8/2018 | 6/8/2018 11:48:29 AM | P | CANC |
|
|
Per Rand this will be rescheduled for monday or tuesday.
Rand Phone #: ###-####
|
BLD17-00747
| FIRE-Final Inspection | 6/8/2018 | 6/8/2018 | 6/8/2018 11:34:11 AM | P | CANC |
|
|
To be rescheduled per Jade until he can get pland and small documents on site.
Jade Conrad Phone #: ###-####
|
FIR18-00045
| INSP-Final Inspection | 6/7/2018 | 6/8/2018 | 6/8/2018 11:28:40 AM | A | FAIL |
|
|
We tested the duct smoke detector for shutdown and it functioned but the issue is per Potter tech support this duct detector, DDA, is not for outdoor use. A different detector listed for outdoor use, maybe with an enclosure, is going to need to be submitted/approved/installed and tested.
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR17-00198
| INSP-Sprinkler Rough-in/Hydro | 6/7/2018 | 6/8/2018 | 6/8/2018 9:18:36 AM | A | PASS |
|
|
2nd,3rd floor hydro tests passed.
|
BLD18-01586
| FIRE-Final Inspection | 6/7/2018 | 6/8/2018 | 6/8/2018 8:47:29 AM | A | PASS |
|
|
Life safety passed
SId Phone #: ###-####
|
FIR18-00438
| INSP-Final Inspection | 6/7/2018 | 6/8/2018 | 6/8/2018 8:43:31 AM | A | PASS |
|
|
permit finaled
Tom Phone #: ###-####
|
FIR18-00399
| INSP-Final Inspection | 6/7/2018 | 6/8/2018 | 6/8/2018 8:14:17 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-00665
| FIRE-Final Inspection | 6/7/2018 | 6/8/2018 | 6/8/2018 12:00:00 AM | P | CANC |
|
|
Mark Phone #: ###-####
|
FIR18-00129
| INSP-Final Inspection | 6/7/2018 | 6/8/2018 | 6/7/2018 3:21:06 PM | A | PASS |
|
|
Permit finaled
|