BLD20-01575
| FIRE-Final Inspection | 6/8/2020 | 6/8/2020 | 6/8/2020 3:58:06 PM | P | FAIL |
|
|
Need plans and small documents, need fire extinguishers upstairs and down, need to repair exit sign in warehouse, need single action hardware on doors.screened // Evan Phone #: ###-####
|
FIR20-00074
| INSP-Final Inspection | 6/8/2020 | 6/8/2020 | 6/8/2020 3:56:56 PM | P | PART |
|
|
Phase 2 sprinkler work is complete.
Please Contact Rick Fry for final Inspection. This final is for phase 2 only. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR19-00949
| INSP-Final Inspection | 6/8/2020 | 6/8/2020 | 6/8/2020 3:56:12 PM | P | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR20-00142
| INSP-Final Inspection | 6/4/2020 | 6/8/2020 | 6/8/2020 2:52:45 PM | P | FAIL |
|
|
The smoke detectors need to be centered on the doors as per NFPA 72 (door release). Also care needs to be taken on the air grill as discussed. No testing performed.
Kc Strykowski, Tech Phone #: ###-#### Inspection requested via web by John Siewert
|
FIR19-00888
| INSP-Sprinkler Rough-in | 6/8/2020 | 6/8/2020 | 6/8/2020 2:50:55 PM | P | PART |
|
|
I gave the ok to cover on the remaining underground piping except for the two east most thrust blocks. These two thrust blocks have pulled/fallen away from the underground supply piping and will need to be repoured, re-inspected, prior to an ok for cover.
Bryan Collins is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00949
| INSP-Final Inspection | 6/8/2020 | 6/8/2020 | 6/8/2020 12:46:48 PM | A | PASS |
|
|
Forward flush passed. Permit finaled.
JON IS OUR FOREMAN ON SITE Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
FIR20-00148
| INSP-Final Inspection | 6/5/2020 | 6/8/2020 | 6/8/2020 12:37:45 PM | P | CANC |
|
|
To be rescheduled per Jeremiah.
Looking to final after hydro at some point in the day. Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR20-00148
| INSP-Sprinkler Rough-in/Hydro | 6/5/2020 | 6/8/2020 | 6/8/2020 12:32:27 PM | A | PASS |
|
|
Over head Hydro witnessed with no pressure loss and the remote FDC piping has been coated and wrapped. It is ok to bury.
Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR20-00113
| INSP-Final Inspection | 6/7/2020 | 6/8/2020 | 6/8/2020 10:55:26 AM | A | FAIL |
|
|
All items corrected except we still need to test the duct smoke detectors and get paper work for a final.
Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR20-00115
| INSP-Final Inspection | 6/5/2020 | 6/8/2020 | 6/8/2020 10:54:55 AM | P | CANC |
|
|
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa Inspection cancelled via mobile web on Monday, June 08, 2020.
|
BLD18-02566
| FIRE-Final Inspection | 6/5/2020 | 6/8/2020 | 6/8/2020 10:15:57 AM | A | FAIL |
|
|
Provide emergency lighting, provide fire extinguisher, provide fire sprinkler protection for canopies due to the presence of the fire pit, provide approved hardware/hinge for the gate as discussed, provide signage at the gas valves as discussed.
Ed *screened* Phone #: ###-####
|