Inspections for the day of: Monday, June 9, 1997.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-01242 INSP - Final6/6/19976/9/19976/9/1997 12:00:00 AMAPASS
06/08/97 403 -
ELE97-01680 INSP - T/S and Final6/6/19976/9/19976/9/1997 12:00:00 AMAPASS
06/08/97 403 - SURVEY LEFT. NEC: 250-72(B). GROUNDING ELECTRODE CONDUC CONTINUITY FROM METEL ENCLOSURE TO GROUNDING ELECTRODE.
ELE97-01727 INSP - Permanent service6/6/19976/9/19976/9/1997 12:00:00 AMAFAIL
06/08/97 403 - NEC: 250-80. WATER PIPING SHALL BE BONDED TO SERVICE. N MORE BUILDINGS SHALL EACH HAVE A GROUNDING ELECTRODE SYSTEM. NEC: 230-2 SERVICE MAST SHALL BE GUYED OR BRACED.
ELE97-01797 INSP - Final6/5/19976/9/19976/9/1997 12:00:00 AMAPASS
06/08/97 403 -
ELE97-01825 INSP - Permanent service6/6/19976/9/19976/9/1997 12:00:00 AMANR
06/08/97 403 - CONTRACTOR WILL RESCHEDULE...MB
ELE97-01825 INSP - Permanent service6/9/19976/9/19976/9/1997 12:00:00 AMPPASS
06/09/97 403 - reinspection
ELE97-01849 INSP - Permanent service6/9/19976/9/19976/9/1997 12:00:00 AMPPASS
06/09/97 403 -
ELE97-01850 INSP - Permanent service6/9/19976/9/19976/9/1997 12:00:00 AMPPASS
06/09/97 403 -
ELE97-00493 INSP - Final6/6/19976/9/19976/9/1997 12:00:00 AMPPASS
06/09/97 403 - Late monday afternoon around four. Reinspection for RJ's
ELE97-01808 INSP - Final6/5/19976/9/19976/9/1997 12:00:00 AMPCANC
06/09/97 403 - NEW OPERATIONS BLD/ THIS PERMIT IS FOR LUNCH & BREAKROOM INSPEECTION UNDER THIS PERMIT/ THEY SAY R-IN DONE BY SOMEONE ELSE. HI MA ANGIE. (TAB TO NEXT LINE). FINAL IN BREAKROOM WAS COMPLETED BY ALL ELEC., CANNOT DO FINAL INSPECTION UNTIL PERMIT HAS BEEN ISSUED TO ALL ELECTRIC CO. FOR WORK THEY PERFORMED.
ELE97-01824 INSP - Permanent service6/9/19976/9/19976/9/1997 12:00:00 AMPPASS
ELE97-01824 INSP - Permanent service6/9/19976/9/19976/9/1997 12:00:00 AMPPASS
ELE97-01824 INSP - Final6/9/19976/9/19976/9/1997 12:00:00 AMPPASS
06/09/97 403 - SURVEY LEFT: NEED BONDING JUMPER OF GROUNDING ELECTRODE CONDUCTOR FROM COLD WATER PIPING TO HOT WATER PIPING. SHALL REPLACE OLD METER-HOUSING WITH APPROVED WEATHER PROOF J-BOX, FOR WIRING CONNECTIONS...MB
ELE97-00493 INSP - Final6/5/19976/9/19976/6/1997 12:00:00 AMACANC
RJ'S They talked to you (Marv) and he decided to change it to the afternoon.