ELE97-01242
| INSP - Final | 6/6/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | A | PASS |
|
|
06/08/97 403 -
|
ELE97-01680
| INSP - T/S and Final | 6/6/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | A | PASS |
|
|
06/08/97 403 - SURVEY LEFT. NEC: 250-72(B). GROUNDING ELECTRODE CONDUC CONTINUITY FROM METEL ENCLOSURE TO GROUNDING ELECTRODE.
|
ELE97-01727
| INSP - Permanent service | 6/6/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | A | FAIL |
|
|
06/08/97 403 - NEC: 250-80. WATER PIPING SHALL BE BONDED TO SERVICE. N MORE BUILDINGS SHALL EACH HAVE A GROUNDING ELECTRODE SYSTEM. NEC: 230-2 SERVICE MAST SHALL BE GUYED OR BRACED.
|
ELE97-01797
| INSP - Final | 6/5/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | A | PASS |
|
|
06/08/97 403 -
|
ELE97-01825
| INSP - Permanent service | 6/6/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | A | NR |
|
|
06/08/97 403 - CONTRACTOR WILL RESCHEDULE...MB
|
ELE97-01825
| INSP - Permanent service | 6/9/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | PASS |
|
|
06/09/97 403 - reinspection
|
ELE97-01849
| INSP - Permanent service | 6/9/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | PASS |
|
|
06/09/97 403 -
|
ELE97-01850
| INSP - Permanent service | 6/9/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | PASS |
|
|
06/09/97 403 -
|
ELE97-00493
| INSP - Final | 6/6/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | PASS |
|
|
06/09/97 403 - Late monday afternoon around four. Reinspection for RJ's
|
ELE97-01808
| INSP - Final | 6/5/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | CANC |
|
|
06/09/97 403 - NEW OPERATIONS BLD/ THIS PERMIT IS FOR LUNCH & BREAKROOM INSPEECTION UNDER THIS PERMIT/ THEY SAY R-IN DONE BY SOMEONE ELSE. HI MA ANGIE. (TAB TO NEXT LINE). FINAL IN BREAKROOM WAS COMPLETED BY ALL ELEC., CANNOT DO FINAL INSPECTION UNTIL PERMIT HAS BEEN ISSUED TO ALL ELECTRIC CO. FOR WORK THEY PERFORMED.
|
ELE97-01824
| INSP - Permanent service | 6/9/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | PASS |
|
|
|
ELE97-01824
| INSP - Permanent service | 6/9/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | PASS |
|
|
|
ELE97-01824
| INSP - Final | 6/9/1997 | 6/9/1997 | 6/9/1997 12:00:00 AM | P | PASS |
|
|
06/09/97 403 - SURVEY LEFT: NEED BONDING JUMPER OF GROUNDING ELECTRODE CONDUCTOR FROM COLD WATER PIPING TO HOT WATER PIPING. SHALL REPLACE OLD METER-HOUSING WITH APPROVED WEATHER PROOF J-BOX, FOR WIRING CONNECTIONS...MB
|
ELE97-00493
| INSP - Final | 6/5/1997 | 6/9/1997 | 6/6/1997 12:00:00 AM | A | CANC |
|
|
RJ'S They talked to you (Marv) and he decided to change it to the afternoon.
|