FIR03-00081
| FIR-Aging Inspection | 6/9/2003 | 6/9/2003 | 6/9/2003 12:00:00 AM | | NR |
|
|
I spoke to Bob Knight with Shilo and he stated that the contractor is not ready for them to start work yet. 6/9/2003 10:43:55 AM
|
BLD03-00821
| FIRE-Final Inspection | 6/9/2003 | 6/9/2003 | 6/9/2003 12:00:00 AM | P | FAIL |
|
|
wayne ; Phone #: ###-#### Heads in showroom area are overspaced. Provide approved fire sprinkler plans as per note #7. There was no access to verify if the fire alarm system was code compliant per note #9, the contractor to verify. Exit sign in office does not appear to have the required battery backup. Provide approved door hardware per review note # 15 and the approved drawings. Verify yearly inspection has been performed on the fire sprinkler riser per review note #21. 6/9/2003 4:13:45 PM
|