Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01166 Final6/8/20066/9/20066/9/2006 3:53:13 PMPPASS
mike - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ok card signed called electrician and met with owner on cords for pendent fixtures for display
ELE05-04648 Electrical Rough-In6/9/20066/9/20066/9/2006 3:51:43 PMPPASS
john call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-02102 Rough-In Permanent Service6/8/20066/9/20066/9/2006 2:01:23 PMPPASS
SPA AND SERVICE UPGRADE; Phone #: ###-#### Internet Inspection Request from: Barry Kendall r/i p/s o/h rec. ok
ELE06-02102 Final6/9/20066/9/20066/9/2006 2:00:54 PMPPASS
SPA AND SERVICE UPGRADE; Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok corr. made
ELE06-02115 Permanent Service6/8/20066/9/20066/9/2006 1:37:22 PMPFAIL
don; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr called 110.26(F)(2) shall remove phone equipment from below p/s, 230.28 phone cable shall be removed from service mast note final that was done on original permit , was with power electrician hooked up not ID power electrician never called for p/s on job
ELE05-04417 Permanent Service6/9/20066/9/20066/9/2006 12:50:49 PMPPASS
steve; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
p/s u/g new for house meter
ELE06-02116 Rough-In Permanent Service6/8/20066/9/20066/9/2006 11:01:49 AMAPART
UFER GROUND INSPECTION; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok
ELE06-01633 Permanent Service6/8/20066/9/20066/9/2006 11:01:31 AMAPASS
marvin - #114; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley

p/s u/g for meter space #114
ELE06-00609 Final6/8/20066/9/20066/9/2006 10:28:21 AMAPASS
Ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles final ok no card, floor outlets will be completed on permit
ele06-02123
ELE06-01578 Electrical Rough-In6/8/20066/9/20066/9/2006 10:14:51 AMAPASS
peter - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley r/i ok needs #10 equip grd too grd heater bath rm
ELE06-01523 Electrical Rough-In6/8/20066/9/20066/9/2006 9:59:45 AMAFAIL
Internet Inspection Request from: Tyler Bowen corr. fee due called314.16 box fill ,314.43 screws in plastic boxes, 314.17(A&C) replace all boxes cutin and 2 gang with broken clamps, 210.70 needs fixture or fixtures too light stairs, 210.52(A) outlet spacing
ELE06-01930 Permanent Service6/8/20066/9/20066/9/2006 8:43:51 AMAFAIL
bill - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
corr. called 250.24(A)(5) remove GEC and isolate it form grounded bus in subpanels
ELE05-03535 Final6/8/20066/9/20066/8/2006 2:23:27 PMPPASS
Nickoli; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
final ok correction made by electrical contr. permit ele06-02117
ELE06-02117 Final6/8/20066/9/20066/8/2006 2:22:11 PMAPASS
###-#### - allen only responsible for correcting the violations posted too owner's permit ele05-03535 final ok