ELE08-00296
| Electrical Rough-In | 6/9/2008 | 6/9/2008 | 6/9/2008 3:58:22 PM | P | PART |
|
|
New wall inspection inside existing building. Phone #: ###-#### Internet Inspection Request from: Karl Paige ok to cover all walls except north wall of big room
|
ESC08-00168
| General Inspection | 6/9/2008 | 6/9/2008 | 6/9/2008 3:28:13 PM | P | PASS |
|
|
looked ok
|
ESC07-01520
| Random Inspection | 6/9/2008 | 6/9/2008 | 6/9/2008 3:26:29 PM | P | PART |
|
|
looked ok
|
ESC08-00328
| General Inspection | 6/9/2008 | 6/9/2008 | 6/9/2008 3:25:14 PM | P | PART |
|
|
looked ok
|
ELE08-01000
| Electrical Rough-In | 6/9/2008 | 6/9/2008 | 6/9/2008 3:23:32 PM | P | PASS |
|
|
wes - bathroom Phone #: ###-#### ok to cover bath
|
ELE08-01382
| Final | 6/9/2008 | 6/9/2008 | 6/9/2008 3:22:01 PM | P | CANC |
|
|
William; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see ri
|
ELE08-01382
| Electrical Rough-In | 6/9/2008 | 6/9/2008 | 6/9/2008 3:21:31 PM | P | PASS |
|
|
William; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ri ok, ok to cover trench
|
ELE08-01315
| Final | 6/9/2008 | 6/9/2008 | 6/9/2008 2:00:18 PM | P | FAIL |
|
|
Neil Phone #: ###-#### called, left corredction notice, NEC 330.30(B) mc cable shall be secured within 12" of termination, 725.3(B) abandoned class 2, 3, pltc cable shall be removed, no esc
|
ELE08-01542
| Electrical Rough-In | 6/9/2008 | 6/9/2008 | 6/9/2008 12:50:37 PM | P | FAIL |
|
|
please inspect boxes and condiut for floor outlets. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called, left message, left correction notice,BCC shall inspect u/g before cover, no esc
|
ELE08-01548
| Electrical Rough-In | 6/9/2008 | 6/9/2008 | 6/9/2008 12:47:43 PM | P | FAIL |
|
|
Kubik electric Phone #: ###-#### called left correction notice, NEC edge of bored holes and mc cable shall be 1 1/4" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of boxes, BCC plans and layout do not agree, no esc
|
ELE06-04394
| Final | 6/9/2008 | 6/9/2008 | 6/9/2008 10:45:54 AM | A | PASS |
|
|
ok to final, no esc
|
ELE08-01539
| Final | 6/9/2008 | 6/9/2008 | 6/9/2008 9:59:54 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final, no esc
|
ELE08-01503
| Electrical Rough-In | 6/4/2008 | 6/9/2008 | 6/9/2008 9:38:26 AM | A | PASS |
|
|
Two outlets in living room are ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ric ok, no esc
|
ELE08-01503
| Final | 6/9/2008 | 6/9/2008 | 6/9/2008 9:32:28 AM | P | PASS |
|
|
Two outlets in living room are ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ok to final, no esc
|
ELE08-01358
| Rough-In Permanent Service | 6/5/2008 | 6/9/2008 | 6/6/2008 7:38:04 AM | A | CANC |
|
|
Steve Phone #: ###-#### Disp set to [CANC] by a contractor via Hello! on Jun 6 2008 7:38AM.
|