Inspections for the day of: Monday, June 9, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00296 Electrical Rough-In6/9/20086/9/20086/9/2008 3:58:22 PMPPART
New wall inspection inside existing building. Phone #: ###-#### Internet Inspection Request from: Karl Paige ok to cover all walls except north wall of big room
ESC08-00168 General Inspection6/9/20086/9/20086/9/2008 3:28:13 PMPPASS
looked ok
ESC07-01520 Random Inspection6/9/20086/9/20086/9/2008 3:26:29 PMPPART
looked ok
ESC08-00328 General Inspection6/9/20086/9/20086/9/2008 3:25:14 PMPPART
looked ok
ELE08-01000 Electrical Rough-In6/9/20086/9/20086/9/2008 3:23:32 PMPPASS
wes - bathroom Phone #: ###-#### ok to cover bath
ELE08-01382 Final6/9/20086/9/20086/9/2008 3:22:01 PMPCANC
William; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see ri
ELE08-01382 Electrical Rough-In6/9/20086/9/20086/9/2008 3:21:31 PMPPASS
William; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ri ok, ok to cover trench
ELE08-01315 Final6/9/20086/9/20086/9/2008 2:00:18 PMPFAIL
Neil Phone #: ###-#### called, left corredction notice, NEC 330.30(B) mc cable shall be secured within 12" of termination, 725.3(B) abandoned class 2, 3, pltc cable shall be removed, no esc
ELE08-01542 Electrical Rough-In6/9/20086/9/20086/9/2008 12:50:37 PMPFAIL
please inspect boxes and condiut for floor outlets. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called, left message, left correction notice,BCC shall inspect u/g before cover, no esc
ELE08-01548 Electrical Rough-In6/9/20086/9/20086/9/2008 12:47:43 PMPFAIL
Kubik electric Phone #: ###-#### called left correction notice, NEC edge of bored holes and mc cable shall be 1 1/4" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of boxes, BCC plans and layout do not agree, no esc
ELE06-04394 Final6/9/20086/9/20086/9/2008 10:45:54 AMAPASS
ok to final, no esc
ELE08-01539 Final6/9/20086/9/20086/9/2008 9:59:54 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final, no esc
ELE08-01503 Electrical Rough-In6/4/20086/9/20086/9/2008 9:38:26 AMAPASS
Two outlets in living room are ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ric ok, no esc
ELE08-01503 Final6/9/20086/9/20086/9/2008 9:32:28 AMPPASS
Two outlets in living room are ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ok to final, no esc
ELE08-01358 Rough-In Permanent Service6/5/20086/9/20086/6/2008 7:38:04 AMACANC
Steve Phone #: ###-#### Disp set to [CANC] by a contractor via Hello! on Jun 6 2008 7:38AM.