FIR09-00254
| INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/10/2009 2:11:55 PM | P | PASS |
|
|
permit finaled
|
BLD08-01664
| FIRE-Final Inspection | 6/9/2009 | 6/9/2009 | 6/10/2009 7:09:22 AM | P | PASS |
|
|
life safety passed
|
FIR09-00097
| INSP-Alarm Testing | 6/9/2009 | 6/9/2009 | 6/10/2009 7:08:15 AM | P | DONE |
|
|
This was a rough-in inspection for the center building third floor fire alarm system which passed.
|
BLD09-00864
| FIRE-Final Inspection | 6/5/2009 | 6/9/2009 | 6/9/2009 2:51:34 PM | A | FAIL |
|
|
See the city approved plans for corrections needed and their locations. They include exit signs, emergency lights, fire extinguishers, racking permit, door hardware and fire rated assemblies.
|
BLD08-00475
| FIRE-Conference | 6/9/2009 | 6/9/2009 | 6/9/2009 2:50:18 PM | P | DONE |
|
|
The curtains along the south wall can not block the required exit doors at any time. The south exit door in the main library is required and atleast one of the south facing doors in the southeast corner room is required.
|
FIR08-00603
| INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 2:48:40 PM | A | FAIL |
|
|
All items tested ok except for the hvac interconnect has not been terminated. The curtains in the south east room rolled up under alarm but the curtains in the main library room did not. Another inspection fee is to be applied.
|
FIR08-00706
| INSP-Final Inspection | 6/9/2009 | 6/9/2009 | 6/9/2009 2:45:41 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00340
| INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 2:44:23 PM | A | PASS |
|
|
Permit finaled
|
FIR08-00810
| INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 11:21:53 AM | A | CANC |
|
|
Ray McQueen Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
FIR09-00130
| INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 11:13:11 AM | A | PASS |
|
|
Permit finaled
|
FIR08-00143
| INSP-Final Inspection | 6/9/2009 | 6/9/2009 | 6/9/2009 11:01:46 AM | P | FAIL |
|
|
The elevator contractor could not find a reset key at first. After the key was found the beam detector in the main corridor was tested. The elevator recalled to the second floor but would not reset. The elevator contractor was trying to trouble shoot the problem when I left.
|
BLD09-00393
| FIRE-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 9:59:56 AM | A | PASS |
|
|
Life safety passed.
|
FIR09-00355
| INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 9:59:22 AM | A | PASS |
|
|
permit finaled
|