Inspections for the day of: Wednesday, June 9, 2010.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02250 ELE-Aging Inspection6/9/20106/9/20106/15/2010 3:48:49 PM CANC
ELE09-02369 ELE-Aging Inspection6/9/20106/9/20106/15/2010 3:48:37 PM CANC
ELE10-00701 Final6/9/20106/9/20106/9/2010 3:36:27 PMPFAIL
rocky Phone #: ###-#### called
ELE10-01249 Permanent Service6/9/20106/9/20106/9/2010 2:46:17 PMPPASS
Dan Phone #: ###-#### p/s u/g rec. ok
ELE10-01249 Final6/9/20106/9/20106/9/2010 2:45:58 PMPPASS
Dan Phone #: ###-####
ELE10-01099 Permanent Service6/8/20106/9/20106/9/2010 2:00:05 PMPPASS
Neil Phone #: ###-#### p/s u/g rec. ok
ELE10-01245 Rough-In Permanent Service6/9/20106/9/20106/9/2010 1:12:38 PMPPASS
Please inspect the Meter/Panel on the South side of the house that we changed. Please call the Home Owner, Coleman at ###-#### to meet you at the house. Our Electrician that performed the work is Mark at ###-####. Please also perform a Final for this so that Idaho Power will turn the power back on for the customer today. Thank you. This home is occupied. Inspection requested from web by: Clint Tate Phone #: ###-#### address range and dryer recepts and pigtails, bond water to p/s remove bond from subpanel, workbench under subpanel shall be removeable p/s u/g rec. ok
ELE10-00937 Final6/8/20106/9/20106/9/2010 12:23:53 PMAFAIL
garage code is 02430 Inspection requested from web by: Joe Thomas Phone #: ###-#### called corr. 314.16 box fill pen. counter, MB closet fixture clearence
ELE10-01246 Final6/8/20106/9/20106/9/2010 12:12:44 PMAPART
Contact Spencer prior to inspection for access or if there are any questions. ###-#### Inspection requested from web by: Spencer Mclean Phone #: ###-####
ELE10-01248 Electrical Rough-In6/8/20106/9/20106/9/2010 12:12:22 PMAFAIL
Inspection requested from web by: daniel bibikov Phone #: ###-#### protect cables attic
ELE10-01248 Permanent Service6/9/20106/9/20106/9/2010 12:11:15 PMAPASS
p/s u/g new ok
ELE10-00943 Electrical Rough-In6/8/20106/9/20106/9/2010 10:58:22 AMAPASS
Dave Phone #: ###-#### conduit deck
ELE10-01226 Final6/3/20106/9/20106/9/2010 10:57:42 AMAPASS
Inspection requested from web by: Clint Tate Phone #: ###-####
ELE10-01226 Electrical Rough-In6/9/20106/9/20106/9/2010 10:57:29 AMAPASS
Inspection requested from web by: Clint Tate Phone #: ###-####
ELE10-00625 Rough-In Permanent Service6/8/20106/9/20106/9/2010 9:16:53 AMAFAIL
The contact for this is Mike TenHulzen Inspection requested from web by: Jamie Winters Phone #: ###-#### met contr GEC shall terminate at neutral bus, also needs sq D bonding means and equip grd kit, x former grding shall be at X/O terminal not the enclosure
ELE10-01258 Electrical Rough-In6/8/20106/9/20106/9/2010 8:44:16 AMAPASS
Mike-Bonding and light inspection please Phone #: ###-####
ELE10-01255 Electrical Rough-In6/8/20106/9/20106/9/2010 7:34:00 AMAPASS
need underground trench inspection Inspection requested from web by: Lloyd Looney Phone #: ###-#### ok
ELE10-01246 Final6/7/20106/9/20106/8/2010 3:07:20 PMACANC
Please contact Clay Jackson if there are any questions Inspection requested from web by: Spencer Mclean Phone #: ###-#### Inspection cancelled from web by: Spencer Mclean