Inspections for the day of: Wednesday, June 9, 2010.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01229 Electrical Rough-In6/9/20106/9/20106/9/2010 2:49:30 PMPPART
Eric Phone #: ###-#### ok to cover 2 floor boxes ne part
ELE09-01423 Final6/9/20106/9/20106/9/2010 2:23:07 PMPFAIL
Inspection requested from web by: Brandon Blackham Phone #: ###-#### called, left message, left correction notice, NEC210.52(C)(1) receptace shall be nmounted within 24" of sink edge, 210.52(A)(2)(3) shall provide convenience receptacles below bar type counter, 314.20 shall provide cover for box in utility room, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-01244 Electrical Rough-In6/7/20106/9/20106/9/2010 1:28:06 PMPFAIL
Inspection requested from web by: Louis Keller Phone #: ###-#### called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 shall provide circuit directory that is clear, concise and explanatory, 110.22(A) shall identify disconnects and be durable enough to withstand the environment, 110.26 shall provide work space about sub-panel in garage
ELE10-00955 Permanent Service6/8/20106/9/20106/9/2010 12:28:38 PMPNR
Phone #: ###-#### called, said to call when done
ELE10-01257 Conference6/8/20106/9/20106/9/2010 11:35:43 AMADONE
Phillip Phone #: ###-#### - call 30 mins prior to going talked about wiring remodel area, code items, when to call for ri inspection
ELE10-01218 Final6/8/20106/9/20106/9/2010 10:42:37 AMAPASS
david Phone #: ###-#### ok to final
ELE10-01251 Permanent Service6/8/20106/9/20106/9/2010 10:37:24 AMPCANC
Inspection requested from web by: TOM BICANDI Phone #: ###-#### Inspection cancelled from web by: TOM BICANDI
ELE10-01261 Electrical Rough-In6/8/20106/9/20106/9/2010 10:19:08 AMAPASS
well be ready after 10:00 Inspection requested from web by: Roy Kay Phone #: ###-#### ric ok
ELE10-00612 Final6/8/20106/9/20106/9/2010 9:54:09 AMAPASS
Please call first for lock box code. final service and downstairs repairs. Inspection requested from web by: Steve Ruter Phone #: ###-#### called, ok to final
ELE10-01256 Temporary Service6/8/20106/9/20106/9/2010 9:18:03 AMAPASS
THANKS, BOB Inspection requested from web by: Bob Glenn Phone #: ###-#### t/s u/g n ok
ELE10-01237 Rough-In Permanent Service6/8/20106/9/20106/9/2010 8:36:10 AMAPASS
Inspection requested from web by: Zane Robertson Phone #: ###-#### corrections made, ric ok, p/s u/g n ok
ELE10-00991 Final6/8/20106/9/20106/9/2010 8:04:48 AMAPASS
bruce Phone #: ###-#### ok to final
ELE09-01437 Final6/9/20106/9/20106/9/2010 7:23:08 AMAPASS
ok to final
ELE07-01553 ELE-Aging Inspection6/9/20106/9/20106/9/2010 7:20:42 AM DONE
see doc expire
ELE07-01553 DOC - Permit Expired6/9/20106/9/20106/9/2010 7:20:30 AMAPASS
no activity
ELE07-01238 ELE-Aging Inspection6/9/20106/9/20106/9/2010 7:19:25 AM DONE
see doc expire
ELE07-01238 DOC - Permit Expired6/9/20106/9/20106/9/2010 7:19:13 AMAPASS