ELE11-00978
| Final | 6/9/2011 | 6/9/2011 | 6/9/2011 2:56:54 PM | P | PART |
|
|
Kevin Phone #: ###-#### ok except for NEC 210.63, show room receptacles, did not sign card
|
ELE09-01497
| Final | 6/9/2011 | 6/9/2011 | 6/9/2011 2:51:47 PM | P | PASS |
|
|
Mike is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates ok to final
|
ELE11-00305
| Electrical Rough-In | 6/8/2011 | 6/9/2011 | 6/9/2011 2:19:10 PM | P | PART |
|
|
Contact: Roger Marose - Rough-in and underground inspection please. Phone #: ###-#### >> Inspection requested via web by Deb Gooden ok u/g loading dock area, walls office area 1st floor only
|
ELE11-01002
| Final | 6/9/2011 | 6/9/2011 | 6/9/2011 1:23:15 PM | P | PASS |
|
|
contact homeowner for access. earl afternoon preferred if possible Phone #: ###-#### >> Inspection requested via web by Mike Swift ok final
|
ELE11-01072
| Electrical Rough-In | 6/8/2011 | 6/9/2011 | 6/9/2011 12:37:39 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld ok cover u/g only
|
ELE11-01183
| Electrical Rough-In | 6/9/2011 | 6/9/2011 | 6/9/2011 12:07:50 PM | P | NR |
|
|
Jon Phone #: ###-#### >> Inspection requested via web by Sean DeLacy just started job, wanted for Friday
|
ELE11-01176
| Permanent Service | 6/8/2011 | 6/9/2011 | 6/9/2011 10:29:49 AM | A | FAIL |
|
|
Kenny Phone #: ###-#### corrections not made, called and told to fix before inspection
|
ELE11-01034
| Permanent Service | 6/8/2011 | 6/9/2011 | 6/9/2011 10:22:24 AM | A | PASS |
|
|
There hasnt been a meter installed over a year, IP is requiring an insp. of the service, we fixed the (2) corrections of: updating the grounding and secure the riser. thanks. Phone #: ###-#### >> Inspection requested via web by Stephen Kren corrections made, p/s o/h rec ok
|
ELE11-01201
| Electrical Rough-In | 6/8/2011 | 6/9/2011 | 6/9/2011 9:49:44 AM | A | FAIL |
|
|
Call Steve at ###-#### prior to inspection Phone #: ###-#### >> Inspection requested via web by Steve Craig called. left correction notice, NEC330.17 shall protect mc cable per 300.4(A)&(D), 330.30B shall strap mc within 12" of box, 348.30 A,B shall strap and support flex metal conduit, 358.26 there shall not be more than 360 degree bend in emt, BCC shall not support mc in valley of studs
|
ELE11-01197
| Electrical Rough-In | 6/8/2011 | 6/9/2011 | 6/9/2011 9:05:15 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot ri ok
|
ELE10-02827
| Final | 6/8/2011 | 6/9/2011 | 6/9/2011 8:51:54 AM | A | PASS |
|
|
Garage code 0987 enter. Phone #: ###-#### >> Inspection requested via web by Lynn Solmon ok final
|
ELE11-00739
| Final | 6/8/2011 | 6/9/2011 | 6/9/2011 8:31:30 AM | A | PASS |
|
|
Jim called Jack Frank early 6-8 and cancelled today''s inspection as the floors are being done. House will be unlocked for this Thursday final inspection request. Thanks. Phone #: ###-#### >> Inspection requested via web by Paula Gratiot ok final
|
ELE10-01669
| ELE-Aging Inspection | 6/9/2011 | 6/9/2011 | 6/9/2011 6:21:17 AM | | DONE |
|
|
still under construction
|