Inspections for the day of: Monday, June 9, 2014.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02817 ELE-Aging Inspection6/9/20146/9/20146/9/2014 2:23:22 PM DONE
Electrical contractor trying to locate property owner
ELE14-01358 Electrical Rough-In6/8/20146/9/20146/9/2014 2:13:23 PMPNR
underground conduit Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Not ready at this time, NEC 517.13(A)
ELE14-01467 Temporary Service6/6/20146/9/20146/9/2014 9:32:40 AMAFAIL
temp pole Phone #: ###-#### >> Inspection requested via web by Stephen Kren NEC 250.53(G) Electrode shall be installed at least 8ft. in contact with the soil.
ELE14-01466 Temporary Service6/6/20146/9/20146/9/2014 9:30:05 AMAPASS
temp pole, any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren t/s u/g n ok
ELE14-01474 Final6/6/20146/9/20146/9/2014 8:59:35 AMAFAIL
Terry Cushing is contact, ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Pierce Disconnecting means requires dead front for ejector pump. NEC Table 300.5 Requires 18 in depth of PVC conduit
ELE14-01473 Electrical Rough-In6/9/20146/9/20146/9/2014 8:24:11 AMAPASS
robert Phone #: ###-#### rough-in ok