Inspections for the day of: Thursday, June 9, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00324 INSP-Final Inspection6/8/20166/9/20166/9/2016 2:28:36 PMPCANC
To be rescheduled for tomorrow morning for a hydro.
BLD16-02002 FIRE-Final Inspection6/8/20166/9/20166/9/2016 1:53:50 PMAFAIL
Provide sticker at exit door, porvide ADA single action hardware at the exit door, remove the thumbturn deadbolt at the exit door (keyed ok), mount the fire extinguisher. I let the tenant know that the building inspector may require all interior hardware to be ADA
FIR16-00131 INSP-Supply line flush6/6/20166/9/20166/9/2016 1:15:31 PMPPASS
Certification fo the two fire pumps passed today. Papaer work to be provided when finalized.
FIR15-00891 INSP-Final Inspection6/9/20166/9/20166/9/2016 12:17:21 PMPPASS
permit finaled
FIR15-00891 INSP-Alarm Testing6/9/20166/9/20166/9/2016 12:16:18 PMPPASS
Permit finaled
FIR16-00324 INSP-Sprinkler Rough-in/Hydro6/8/20166/9/20166/9/2016 11:26:52 AMAPART
General rough-in passed. Earth quake bracing has not been installed yet. Need more supply pipe installed prior to hydro test. Need as-builts showing the four additional heads installed on kick backs on the west end of the system. The combustible concealed spaces/double walls will need to be addressed prior to a cover inspection.
FIR16-00105 INSP-Supply line flush6/8/20166/9/20166/9/2016 9:35:55 AMAPASS
Underground supply line flush passed
FIR15-00891 INSP-Alarm Testing6/8/20166/9/20166/9/2016 7:15:38 AMAFAIL
South pull station is too low, north pull station is too high and no signals went to the monitoring station