Inspections for the day of: Friday, June 9, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04017 Electrical Rough-In6/9/20176/9/20176/9/2017 3:25:05 PMPPASS
L2 deck pour 10 Phone #: ###-#### Inspection requested via web by Debby Pierce
Area noted rough in ok cover
ELE17-01768 Permanent Service6/9/20176/9/20176/9/2017 3:24:49 PMPPASS
Labels not complete and RV circuit being installed. p/s o/h rec ok
ELE17-00913 Electrical Rough-In6/8/20176/9/20176/9/2017 2:22:17 PMPPASS
Gary is the site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker
Discussed adding show window receptacles north and south windows and watch load calculation due to 20' sections.
Wall rough in ok cover
ELE17-01719 Final6/8/20176/9/20176/9/2017 12:45:32 PMAPASS
Please call 30 min ahead to meet. Phone #: ###-#### Inspection requested via web by Casey Fouts Final ok
ELE17-01476 Conference6/7/20176/9/20176/9/2017 11:44:11 AMADONE
mark Phone #: ###-####
For detached garage discussed 100a feeders, seperate grounded and grounding with concrete encased, GFCI protection for all 15 and 20 amp 120 volt receptacles inside and out, WR for out recept., wiring in NM cable if all horizontal runs protected from physical damage as garage wall cover to be done in future.
ELE17-00927 Final6/8/20176/9/20176/9/2017 11:00:03 AMAPASS
CALL BUILDER FOR ACCESS BEFORE ARRIVAL, GARY ###-#### Phone #: ###-#### Inspection requested via web by mike brown
Final ok
ELE17-01279 Rough-In Permanent Service6/8/20176/9/20176/9/2017 9:43:44 AMAFAIL
ready now. thanks Phone #: ###-#### Inspection requested via web by Bob Glenn
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. Nail plated needed.
Pantry notched stud, Master bed upper plate between windows, spare bed inside closet.
422.11- Furnace branch circuit shall be 20 amp as per manufacturers instructions.
ELE17-01289 Permanent Service6/5/20176/9/20176/8/2017 8:44:39 AMACANC
Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden Duplicate request
ELE17-01286 Permanent Service6/5/20176/9/20176/8/2017 8:44:18 AMACANC
Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden duplicate request