Inspections for the day of: Friday, June 9, 2017.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-02290 Final6/9/20176/9/20176/9/2017 3:42:52 PMPPASS
Call Norma for access: ###-#### Phone #: ###-#### Inspection requested via web by jamie berg
MEC17-02230 Final6/7/20176/9/20176/9/2017 3:29:52 PMPFAIL
Please call customer ahead ###-####. If any questions feel free to call Value Heating ###-####, thank you. Inspection requested via web by Dan Ricken- need uv protection on lineset outddors by A/C- need secondary drain from coil ran out or wet switch- primary drain cant have wet switch installed in it
MEC17-02286 Final6/9/20176/9/20176/9/2017 3:08:31 PMPPASS
Call Max if you need anything ###-####. Thanks Inspection requested via web by Floyd Floyd Peek
MEC17-02286 Pressure Test6/9/20176/9/20176/9/2017 3:08:10 PMPPASS
For flue. Call Max if you need anything ###-####. Thanks Inspection requested via web by Floyd Floyd Peek- 5lb flue pass
MEC17-02108 Final6/5/20176/9/20176/9/2017 3:06:45 PMPPASS
Please inspect after 2 PM. Phone #: ###-#### Inspection requested via web by Mary LaFayette-
MEC17-02149 Final6/9/20176/9/20176/9/2017 2:43:21 PMPPASS
Would like mid PM and call on way. Thank you Phone #: ###-#### Inspection requested via web by Xanti Berria
MEC17-02287 Final6/9/20176/9/20176/9/2017 1:57:38 PMPPASS
Phone #: ###-#### Inspection requested via web by Marisa Hone
MEC17-00901 Final6/8/20176/9/20176/9/2017 1:33:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC17-02101 Rough-in6/8/20176/9/20176/9/2017 11:32:24 AMAFAIL
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- supply plenum in crawl needs insulated- bath fan in master bath needs hooked up- dryer vent 2nd floor needs support in wall or every 4 feet- R/A wye branch 2nd floor attic needs sealed- left correction notice front window
MEC17-02101 Pressure Test6/8/20176/9/20176/9/2017 11:30:03 AMAPASS
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass- 5 lb flue pass
MEC17-02196 Final6/5/20176/9/20176/9/2017 11:08:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Marisa Hone
MEC16-04936 Mec-Aging Inspection6/9/20176/9/20176/9/2017 10:34:23 AM CANC
work in progress- talked with homeowner-
MEC17-02035 Final6/6/20176/9/20176/9/2017 10:08:50 AMAFAIL
Homeowner Betty Oakes ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- need right size breaker in panel- need to seal weather tite whip thru foundation at A/C
MEC16-04972 Final6/8/20176/9/20176/9/2017 9:28:13 AMAFAIL
Call Eric with any issues @ 412.6613 - Home owner is Clio @ ###-#### Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- need air balance report- need to insulate return air plenum
MEC17-02291 Final6/9/20176/9/20176/9/2017 9:27:32 AMAFAIL
remove silicone from wall penetration and fire caulk it
MEC17-02155 Final6/6/20176/9/20176/9/2017 8:50:22 AMAPASS
Please inspect as early as possible and call homeowner, Carolina Matos, at ###-#### prior to inspection Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC17-02106 Final6/9/20176/9/20176/9/2017 8:13:00 AMAPASS
correction made