Inspections for the day of: Friday, June 9, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01806 Conference6/9/20176/9/20176/9/2017 2:42:30 PMPPASS
spoke with homeowner on phone and discussed job....understands bath outlets will be gfi protected...no other circuitry will be on outlet circuit...adding bath vanity light, exhaust fan, and closet light on seperate circuit
ELE17-01560 Final6/9/20176/9/20176/9/2017 12:50:09 PMPFAIL
Phone #: ###-#### Inspection requested via web by Matthew White....

1) intersystem bond shall be added at service location...770.100

2) breakers shall be installed such that the center of the grip of the operating handle of circuit breaker is not more than 6 ft 7 inches....404.8
ELE17-01756 Electrical Rough-In6/9/20176/9/20176/9/2017 11:49:50 AMPPASS
Please call prior to arrival for access. Phone #: ###-#### Inspection requested via web by Patrick Paz...

rough in ok to cover....rearrangement of kitchen...discussed island outlet location...outlet for counterspace in dining rm
ELE17-01777 Rough-In Permanent Service6/8/20176/9/20176/9/2017 10:58:58 AMPPASS
Phone #: ###-#### Inspection requested via web by steve cooper....

rough ok to cover
p/s u/g n ok
ELE17-00980 Final6/8/20176/9/20176/9/2017 10:58:00 AMPPASS
Phone #: ###-#### Inspection requested via web by steve cooper...

ok to final
ELE17-01750 Final6/6/20176/9/20176/9/2017 9:48:31 AMAPASS
Please contact Jennifer at ###-#### for property access. Need to inspect both 1213 S Leadville and 1215 S Leadville (2 circuit extensions) Phone #: ###-#### Inspection requested via web by jamie berg...

correct fuses and wire size for each unit...service outlet WR GFI with inuse cover....ok to final
ELE17-01750 Electrical Rough-In6/9/20176/9/20176/9/2017 9:47:04 AMAPASS
Please contact Jennifer at ###-#### for property access. Need to inspect both 1213 S Leadville and 1215 S Leadville (2 circuit extensions) Phone #: ###-#### Inspection requested via web by jamie berg...

hvac units installed...service outlet installed....fused disconnects used for protection
ELE17-01162 Electrical Rough-In6/8/20176/9/20176/9/2017 9:00:59 AMAPASS
need an above ceiling grid inspection. Phone #: ###-#### Inspection requested via web by Tracy Robertson...

ceiling grid ok