Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01747 Final6/28/20027/1/20027/1/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 06/28/2002 at 13:08:54. Contact: ###-####. ok 7/1/2002 2:55:18 PM
ELE01-02180 Electrical Rough-In6/28/20027/1/20027/1/2002 12:00:00 AMAPART
MARK ###-#### basement and bishop rm ceilings 7/1/2002 10:41:18 AM
ELE02-01997 Electrical Rough-In6/28/20027/1/20027/1/2002 12:00:00 AMAFAIL
HERSCHEL ###-#### PLEASE CALL SO HE CAN LET YOU ON cor. posted called 110.3(B) needs #6 as manufacture states use manufactrues listed breaker 358.22 i/2 conduit not large enough for conductors, 358.12 emt not approved where subject to damage on ground 7/1/2002 1:47:22 PM
ELE02-01956 Electrical Rough-In6/28/20027/1/20027/1/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 06/28/2002 at 15:33:22. Contact: ###-####. cor. posted called 300.4 nail plates and 11/4 inches, 110.12(A) seal unused openings, 314.16 box fill, 250.148 splice all equip grds together, 210.52 (A)(B) outlet spacing in dinning where door was moved, and proper outlet spacing for countertop outlets 7/1/2002 11:21:02 AM
ELE02-01831 Electrical Rough-In7/1/20027/1/20027/1/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 07/01/2002 at 07:09:56. Contact: ###-####. new rm between house and garage 7/1/2002 3:08:14 PM
ELE02-01491 Electrical Rough-In7/1/20027/1/20027/1/2002 12:00:00 AMPPART
for conf ###-#### harold ok no r/i or p/s 7/1/2002 7:33:43 PM
ELE02-01541 Electrical Rough-In7/1/20027/1/20027/1/2002 12:00:00 AMPPART
for conf- ###-####- kenny ok x-ray equip not listed 7/1/2002 4:30:32 PM
ELE02-02003 Electrical Rough-In7/1/20027/1/20027/1/2002 12:00:00 AMPFAIL
r/i rody ###-#### cor. posted called 314.43, 300.4 11/4 and nail plates, 210.52 (A)(B)needs outlet for wall space in new breakfast dinning area, 250.122 needs #12 pigtails not #14, 314.20 all boxes flush for 1/2 rock and outside boxes BCC all make up shall bo complete 7/1/2002 2:42:13 PM
ELE02-02004 Electrical Rough-In7/1/20027/1/20027/1/2002 12:00:00 AMPPART
CONF ONLY DAN ###-#### ok 7/1/2002 3:46:46 PM
ELE02-02004 Permanent Service7/1/20027/1/20027/1/2002 12:00:00 AMPDONE
DAN ###-####
ELE02-02004 Permanent Service7/1/20027/1/20027/1/2002 12:00:00 AMPPASS
p/s o/h rec. ok
ELE02-01598 Electrical Rough-In6/28/20027/1/20027/1/2002 12:00:00 AMPPART
for conf--gary- ###-#### ok new garage, needs concrete encased electrode 7/1/2002 5:16:14 PM