Inspections for the day of: Thursday, July 1, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00528 Final6/30/20047/1/20047/1/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 6/30/2004 at 11:48:33 AM. Contact: ###-####. cor. posted called seal all unused KOs and breaker spaces, isolate all grds and neutral at sub gear, remove old grd wire from old grd rod 7/1/2004 8:44:00 AM
ELE04-01953 Final6/30/20047/1/20047/1/2004 12:00:00 AMAFAIL
Contact: Leon Sheffield; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called 210.8 (B)(3) gfci needed for all recepts in prep,serving area kit, needs listing for all equipment 7/1/2004 10:30:35 AM
ELE04-01972 Final6/30/20047/1/20047/1/2004 12:00:00 AMAPASS
###-#### Pat ok 7/1/2004 9:38:11 AM
ELE04-01882 Permanent Service7/1/20047/1/20047/1/2004 12:00:00 AMAPASS
p/s u/g new ok 7/1/2004 9:38:52 AM
ELE04-01913 Electrical Rough-In6/30/20047/1/20047/1/2004 12:00:00 AMANH
no access called notice posted 7/1/2004 9:37:17 AM
ELE04-01913 Electrical Rough-In7/1/20047/1/20047/1/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 7/1/2004 at 9:18:20 AM. Contact: ###-####. cor. posted called 314.16 314.20 wall fixture box stairwell, 300.4 nail plates and 11/4", 210.52(B) range not allowed on kit circuit 7/1/2004 12:56:04 PM
ELE04-01980 Electrical Rough-In7/1/20047/1/20047/1/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 7/1/2004 at 10:00:46 AM. Contact: ###-####. approval to cover a trench, after 2:00 if possible please. thanks. ok u/g 7/1/2004 3:07:05 PM
ELE04-01326 Final7/1/20047/1/20047/1/2004 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: William Zerfas ok 7/1/2004 3:46:24 PM
ELE04-01913 Permanent Service7/1/20047/1/20047/1/2004 12:00:00 AMPPASS
p/s u/g n ew ok
ELE04-01974 Electrical Rough-In6/30/20047/1/20047/1/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 6/30/2004 at 4:17:05 PM. Contact: ###-####. r/i for u/g and conference ok 7/1/2004 2:23:40 PM