BLD04-00848
| FIRE-Final Inspection | 6/30/2004 | 7/1/2004 | 7/1/2004 12:00:00 AM | A | FAIL |
|
|
Relocate the smoke detector from above to below the ceiling, test it along with the smoke evacuation system. Provide canopy on all sprinkler pendants. 7/1/2004 9:09:45 AM
|
BLD04-00848
| FIRE-Final Inspection | 6/30/2004 | 7/1/2004 | 7/1/2004 12:00:00 AM | P | CANC |
|
|
duplicate inspection 7/1/2004 11:15:47 AM
|
BLD04-00931
| FIRE-Final Inspection | 6/30/2004 | 7/1/2004 | 7/1/2004 12:00:00 AM | P | FAIL |
|
|
sprinkler pendants are overspaced. Provide fire sprinkler permit before correcting work. Provide emergency light in warehouse. Mount fire extinguishers as discussed 7/1/2004 3:21:39 PM
|
FIR03-00453
| INSP-Final Inspection | 7/1/2004 | 7/1/2004 | 7/1/2004 12:00:00 AM | P | PART |
|
|
Tested I-2 section, first floor. See approved plans for specific location and correction. 7/1/2004 4:16:36 PM
|
FIR04-00378
| INSP-Sprinkler Rough-in | 7/1/2004 | 7/1/2004 | 7/1/2004 12:00:00 AM | P | PASS |
|
|
sprinkler piping is ok to cover 7/1/2004 3:19:09 PM
|
BLD04-00469
| FIRE-Final Inspection | 6/30/2004 | 7/1/2004 | 6/30/2004 2:13:30 PM | A | CANC |
|
|
CLINT; Phone #: ###-#### Internet Inspection Request from: Annette Moore Inspection cancelled from web by: Aimee Hughes
|