Inspections for the day of: Friday, July 1, 2005.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02123 Final7/1/20057/1/20057/1/2005 4:12:51 PMPPART
final on swimming pool Internet Inspection Request from: Andy Rose called elect, said we need to see pool cover grounded once it is installed. Pool equip for rest is ok.
ELE05-02174 Final7/1/20057/1/20057/1/2005 4:10:50 PMPPASS
Scheduled by a contractor via Hello! on 7/1/2005 at 9:03:28 AM. Contact: ###-####. signed card, called elect to put on box cover. ok to final
ELE05-02328 Rough-In Permanent Service7/1/20057/1/20057/1/2005 3:09:58 PMPPASS
Scheduled by a contractor via Hello! on 7/1/2005 at 6:21:12 AM. Contact: ###-####. met with owner,left survey, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.8(A),210.11(C)(3) bathroom shall have 20A gfci, 300.4(F) gec shall have abrasion protection, 334.30 nm shall be supported within 12" of box, ric ok, p/s u/g exst ok
ELE05-02344 Permanent Service6/30/20057/1/20057/1/2005 1:43:15 PMPPASS
mobile home///john; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s u/g exst ok
ELE05-02298 Electrical Rough-In6/30/20057/1/20057/1/2005 1:35:15 PMPNH
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called contr and they were supposed to cancel, since they are not ready either. They are having trouble getting access.
ELE05-00656 Final7/1/20057/1/20057/1/2005 12:59:42 PMPFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 352.30(A) rnc shall be strapped within 3' of box,404.9,406.5,314.21 faceplates shall completely cover openings and seat against finished surfaces, (microwave, gec cover, recpts in bedroom), 210.70(A)(2)(a) light shall be in stairway, called contr, left corr notice,
ELE05-02301 Rough-In Permanent Service7/1/20057/1/20057/1/2005 12:26:32 PMPPASS
alan ###-#### ric ok, p/s u/g n ok
ELE05-00465 Final7/1/20057/1/20057/1/2005 10:21:55 AMPPASS
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
ELE05-02311 Temporary Service6/30/20057/1/20057/1/2005 9:53:44 AMAPASS
Scheduled by a contractor via Hello! on 6/30/2005 at 1:56:04 PM. t/s u/g n ok
ELE05-01149 Final7/1/20057/1/20057/1/2005 9:49:57 AMPPASS
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left survey, 404.9 switch faceplates shall seat against surface, 110.12(C) broken recpt plate shall be replaced, ok to final
ELE05-02310 Temporary Service6/30/20057/1/20057/1/2005 9:48:59 AMAPASS
Scheduled by a contractor via Hello! on 6/30/2005 at 1:51:59 PM. Contact: ###-####. t/s u/g n ok
ELE05-02315 Temporary Service6/30/20057/1/20057/1/2005 8:54:29 AMAPASS
Scheduled by a contractor via Hello! on 6/30/2005 at 1:58:49 PM. t/s u/g n ok
ELE05-02313 Temporary Service6/30/20057/1/20057/1/2005 8:53:49 AMAPASS
Scheduled by a contractor via Hello! on 6/30/2005 at 1:54:43 PM. t/s u/g n ok
ELE05-02314 Temporary Service6/30/20057/1/20057/1/2005 8:53:10 AMAPASS
Scheduled by a contractor via Hello! on 6/30/2005 at 1:57:24 PM. t/s u/g n ok
ELE05-02312 Temporary Service6/30/20057/1/20057/1/2005 8:40:24 AMAFAIL
Scheduled by a contractor via Hello! on 6/30/2005 at 1:53:22 PM. called contr, left corr notice, 250.28 bonding jumper shall be installed,fee due
ELE04-03683 Final6/30/20057/1/20057/1/2005 8:32:20 AMAPASS
Scheduled by a contractor via Hello! on 6/30/2005 at 4:35:57 PM. Contact: ###-####. signed occ card, told owner to change 1 bkr to gfci for people, not equip. ok to final
ELE05-02298 Rough-In Permanent Service6/30/20057/1/20056/30/2005 5:01:19 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen Inspection cancelled from web by: Tyler Bowen