ELE05-02123
| Final | 7/1/2005 | 7/1/2005 | 7/1/2005 4:12:51 PM | P | PART |
|
|
final on swimming pool Internet Inspection Request from: Andy Rose called elect, said we need to see pool cover grounded once it is installed. Pool equip for rest is ok.
|
ELE05-02174
| Final | 7/1/2005 | 7/1/2005 | 7/1/2005 4:10:50 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/1/2005 at 9:03:28 AM. Contact: ###-####. signed card, called elect to put on box cover. ok to final
|
ELE05-02328
| Rough-In Permanent Service | 7/1/2005 | 7/1/2005 | 7/1/2005 3:09:58 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/1/2005 at 6:21:12 AM. Contact: ###-####. met with owner,left survey, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.8(A),210.11(C)(3) bathroom shall have 20A gfci, 300.4(F) gec shall have abrasion protection, 334.30 nm shall be supported within 12" of box, ric ok, p/s u/g exst ok
|
ELE05-02344
| Permanent Service | 6/30/2005 | 7/1/2005 | 7/1/2005 1:43:15 PM | P | PASS |
|
|
mobile home///john; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s u/g exst ok
|
ELE05-02298
| Electrical Rough-In | 6/30/2005 | 7/1/2005 | 7/1/2005 1:35:15 PM | P | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called contr and they were supposed to cancel, since they are not ready either. They are having trouble getting access.
|
ELE05-00656
| Final | 7/1/2005 | 7/1/2005 | 7/1/2005 12:59:42 PM | P | FAIL |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 352.30(A) rnc shall be strapped within 3' of box,404.9,406.5,314.21 faceplates shall completely cover openings and seat against finished surfaces, (microwave, gec cover, recpts in bedroom), 210.70(A)(2)(a) light shall be in stairway, called contr, left corr notice,
|
ELE05-02301
| Rough-In Permanent Service | 7/1/2005 | 7/1/2005 | 7/1/2005 12:26:32 PM | P | PASS |
|
|
alan ###-#### ric ok, p/s u/g n ok
|
ELE05-00465
| Final | 7/1/2005 | 7/1/2005 | 7/1/2005 10:21:55 AM | P | PASS |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-02311
| Temporary Service | 6/30/2005 | 7/1/2005 | 7/1/2005 9:53:44 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 1:56:04 PM. t/s u/g n ok
|
ELE05-01149
| Final | 7/1/2005 | 7/1/2005 | 7/1/2005 9:49:57 AM | P | PASS |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left survey, 404.9 switch faceplates shall seat against surface, 110.12(C) broken recpt plate shall be replaced, ok to final
|
ELE05-02310
| Temporary Service | 6/30/2005 | 7/1/2005 | 7/1/2005 9:48:59 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 1:51:59 PM. Contact: ###-####. t/s u/g n ok
|
ELE05-02315
| Temporary Service | 6/30/2005 | 7/1/2005 | 7/1/2005 8:54:29 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 1:58:49 PM. t/s u/g n ok
|
ELE05-02313
| Temporary Service | 6/30/2005 | 7/1/2005 | 7/1/2005 8:53:49 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 1:54:43 PM. t/s u/g n ok
|
ELE05-02314
| Temporary Service | 6/30/2005 | 7/1/2005 | 7/1/2005 8:53:10 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 1:57:24 PM. t/s u/g n ok
|
ELE05-02312
| Temporary Service | 6/30/2005 | 7/1/2005 | 7/1/2005 8:40:24 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 1:53:22 PM. called contr, left corr notice, 250.28 bonding jumper shall be installed,fee due
|
ELE04-03683
| Final | 6/30/2005 | 7/1/2005 | 7/1/2005 8:32:20 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 4:35:57 PM. Contact: ###-####. signed occ card, told owner to change 1 bkr to gfci for people, not equip. ok to final
|
ELE05-02298
| Rough-In Permanent Service | 6/30/2005 | 7/1/2005 | 6/30/2005 5:01:19 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen Inspection cancelled from web by: Tyler Bowen
|