Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00052 FIR-Aging Inspection7/1/20057/1/20057/5/2005 2:32:58 PM DONE
Talked to Bruce at The Security Group ###-#### who said he would look in to the status and return phone call.
FIR05-00045 INSP-Final Inspection7/1/20057/1/20057/1/2005 4:04:49 PMPPART
Overhead hydro test passed, rough-in is good for cover. Need alarms and forward flow tesing prior to final.
FIR05-00277 INSP-Final Inspection7/1/20057/1/20057/1/2005 4:01:52 PMPPART
Overhead hydro passed. Need ceiling tile installed and alarms prior to final.
BLD04-02505 FIRE-Final Inspection7/1/20057/1/20057/1/2005 4:00:38 PMPFAIL
Provide max occ. load sign, provide current inspection tag and install fire ext., repair exit discharge light at back door from kitchen.
FIR05-00383 INSP-Final Inspection7/1/20057/1/20057/1/2005 3:58:33 PMPFAIL
HVAC unit did not shut down upon smoke detection.
FIR05-00062 INSP-Final Inspection7/1/20057/1/20057/1/2005 3:57:24 PMPPART
Need to install two escutcheons on heads in the kitchen area.
FIR05-00313 INSP-Final Inspection7/1/20057/1/20057/1/2005 3:55:58 PMPPART
Hood supression system operated properly under test conditions. Need to provide air balance reports.
FIR05-00252 INSP-Final Inspection7/1/20057/1/20057/1/2005 12:35:47 PMPPASS
Fire alarm finaled.
FIR05-00253 INSP-Final Inspection7/1/20057/1/20057/1/2005 12:34:39 PMPPASS
Fire alarm passed inspection.
FIR05-00284 INSP-Final Inspection6/28/20057/1/20057/1/2005 11:42:18 AMAPASS
Fire alarm finaled.
BLD05-00976 FIRE-Conference6/30/20057/1/20057/1/2005 9:58:12 AMADONE
On site discussion with Kent the GC regarding requirements for the main entry/exit door hardware, swing direction and clear width.
FIR05-00335 INSP-Alarm Testing6/30/20057/1/20057/1/2005 9:22:01 AMAPASS
Fire alarm finaled.
BLD05-01138 FIRE-Final Inspection7/1/20057/1/20057/1/2005 12:00:00 AMAPASS
Fire life safety passed inspection.