Inspections for the day of: Friday, July 1, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00136 FIR-Aging Inspection7/1/20057/1/20057/5/2005 3:00:47 PM NR
Inspection to be called in Thursday per contractor
BLD04-02769 FIRE-Final Inspection7/1/20057/1/20057/1/2005 4:23:43 PMPFAIL
Provide racking permit for the rack storage exceeding 8' in height. Top of rack now is at 11'-10" with storage at 16'-9". Provide one more additional fire extinguisher.
BLD05-01393 FIRE-Final Inspection7/1/20057/1/20057/1/2005 2:37:33 PMPPASS
Fire life safety finaled
BLD04-01721 FIRE-Final Inspection6/30/20057/1/20057/1/2005 2:17:21 PMAPASS
Life safety finaled
FIR03-00082 FIR-Aging Inspection7/1/20057/1/20057/1/2005 2:16:16 PM DONE
I left message at answering service for Jeff Packam for job status
FIR04-00531 INSP-Final Inspection6/29/20057/1/20057/1/2005 1:51:46 PMAPART
Trip tested Dry System #1 and #2. Both sent in the correct alarm signals. Contractor still needs to correct overspaced and blocked heads under canopy, wrong air compressors installed, butterfly control valve on dry system #1 broke, need to blank off the switches controlling the air compressors, need to trip test the east dry system.
BLD05-01393 FIRE-Final Inspection6/30/20057/1/20057/1/2005 11:30:06 AMAFAIL
Remove paddle hardware that is mounted too high on exit door, remove thumbturn on exit door and lower fire extinguisher.
BLD05-01139 FIRE-Final Inspection6/30/20057/1/20057/1/2005 8:47:14 AMAPASS
Life safety finaled
FIR05-00300 INSP-Final Inspection7/1/20057/1/20057/1/2005 8:46:39 AMPPASS
Fire sprinkler finaled
FIR05-00293 INSP-Final Inspection6/30/20057/1/20057/1/2005 8:44:23 AMAPASS
Fire sprinkler finaled
FIR05-00300 INSP-Alarm Testing6/30/20057/1/20057/1/2005 8:43:59 AMAPASS
Fire alarm finaled