FIR05-00136
| FIR-Aging Inspection | 7/1/2005 | 7/1/2005 | 7/5/2005 3:00:47 PM | | NR |
|
|
Inspection to be called in Thursday per contractor
|
BLD04-02769
| FIRE-Final Inspection | 7/1/2005 | 7/1/2005 | 7/1/2005 4:23:43 PM | P | FAIL |
|
|
Provide racking permit for the rack storage exceeding 8' in height. Top of rack now is at 11'-10" with storage at 16'-9". Provide one more additional fire extinguisher.
|
BLD05-01393
| FIRE-Final Inspection | 7/1/2005 | 7/1/2005 | 7/1/2005 2:37:33 PM | P | PASS |
|
|
Fire life safety finaled
|
BLD04-01721
| FIRE-Final Inspection | 6/30/2005 | 7/1/2005 | 7/1/2005 2:17:21 PM | A | PASS |
|
|
Life safety finaled
|
FIR03-00082
| FIR-Aging Inspection | 7/1/2005 | 7/1/2005 | 7/1/2005 2:16:16 PM | | DONE |
|
|
I left message at answering service for Jeff Packam for job status
|
FIR04-00531
| INSP-Final Inspection | 6/29/2005 | 7/1/2005 | 7/1/2005 1:51:46 PM | A | PART |
|
|
Trip tested Dry System #1 and #2. Both sent in the correct alarm signals. Contractor still needs to correct overspaced and blocked heads under canopy, wrong air compressors installed, butterfly control valve on dry system #1 broke, need to blank off the switches controlling the air compressors, need to trip test the east dry system.
|
BLD05-01393
| FIRE-Final Inspection | 6/30/2005 | 7/1/2005 | 7/1/2005 11:30:06 AM | A | FAIL |
|
|
Remove paddle hardware that is mounted too high on exit door, remove thumbturn on exit door and lower fire extinguisher.
|
BLD05-01139
| FIRE-Final Inspection | 6/30/2005 | 7/1/2005 | 7/1/2005 8:47:14 AM | A | PASS |
|
|
Life safety finaled
|
FIR05-00300
| INSP-Final Inspection | 7/1/2005 | 7/1/2005 | 7/1/2005 8:46:39 AM | P | PASS |
|
|
Fire sprinkler finaled
|
FIR05-00293
| INSP-Final Inspection | 6/30/2005 | 7/1/2005 | 7/1/2005 8:44:23 AM | A | PASS |
|
|
Fire sprinkler finaled
|
FIR05-00300
| INSP-Alarm Testing | 6/30/2005 | 7/1/2005 | 7/1/2005 8:43:59 AM | A | PASS |
|
|
Fire alarm finaled
|