ELE08-01798
| Electrical Rough-In | 7/1/2008 | 7/1/2008 | 7/1/2008 4:05:25 PM | P | PART |
|
|
Phone #: ###-#### walls
|
ELE08-01339
| Electrical Rough-In | 6/30/2008 | 7/1/2008 | 7/1/2008 3:01:33 PM | P | PASS |
|
|
Stu Phone #: ###-#### called bond 3/4" emt
|
ELE08-01339
| Final | 7/1/2008 | 7/1/2008 | 7/1/2008 3:01:11 PM | P | PASS |
|
|
Stu Phone #: ###-####
|
ELE08-01796
| Permanent Service | 7/1/2008 | 7/1/2008 | 7/1/2008 2:28:35 PM | P | PASS |
|
|
Randy at ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s u/g rec. ok
|
ELE08-01796
| Final | 7/1/2008 | 7/1/2008 | 7/1/2008 2:28:18 PM | P | PASS |
|
|
Randy at ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok no esc
|
ELE07-01381
| Permanent Service | 7/1/2008 | 7/1/2008 | 7/1/2008 1:57:48 PM | P | PASS |
|
|
wayne Phone #: ###-#### p/s u/g rec. ok
|
ESC08-00019
| Random Inspection | 7/1/2008 | 7/1/2008 | 7/1/2008 1:22:57 PM | P | PART |
|
|
ok
|
ELE08-01681
| Rough-In Permanent Service | 7/1/2008 | 7/1/2008 | 7/1/2008 1:21:14 PM | P | FAIL |
|
|
THANKS JACK............BOB Phone #: ###-#### Internet Inspection Request from: Bob Glenn corr. 110.3, 250.4, 250.120(A) shall use approved tool to crimp grd sleeves 334.23 protect cables at attic accesses, 300.4(D) 11/4" for cables parallel called
|
ELE07-03780
| Final | 7/1/2008 | 7/1/2008 | 7/1/2008 12:15:52 PM | P | PASS |
|
|
ok chiller labeled and listed card signed
|
ELE08-01613
| Final | 6/30/2008 | 7/1/2008 | 7/1/2008 10:01:46 AM | A | FAIL |
|
|
Site combo is 9876. Contact Dave Brakebill (electrician) to access the pre-fab shelter on-site. Phone #: ###-#### Internet Inspection called shall isolate grd and neutrals,250.32, shall install grds and bond wires in clamp lug not between clamp and conduit
|
ESC08-00385
| Random Inspection | 7/1/2008 | 7/1/2008 | 7/1/2008 9:27:29 AM | A | PART |
|
|
ok
|
ELE08-01277
| Final | 6/30/2008 | 7/1/2008 | 7/1/2008 9:13:38 AM | A | FAIL |
|
|
This is a swimming pool. The inspection needed is final. Thx! Internet Inspection Request from: Chris Weimar corr called left message 110.26(F)(1) shall remove gas pipe from below subpanel for required clearence
|
ELE08-01650
| Electrical Rough-In | 6/30/2008 | 7/1/2008 | 7/1/2008 8:28:43 AM | A | PART |
|
|
inspection for underground cover, contact is Toby Groves ###-#### Thank You Phone #: ###-#### Internet Inspection Request from: Debby Ellis S E parking lot u/g ok
|
ELE08-01415
| Rough-In Permanent Service | 6/30/2008 | 7/1/2008 | 6/30/2008 1:43:28 PM | A | CANC |
|
|
Homeowners should be home, if you have any questions, please give Clay a call ###-####. Phone #: ###-#### Internet Inspection Request from: Clay Morgan Inspection cancelled from web by: Clay Morgan
|