Inspections for the day of: Tuesday, July 1, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM08-01525 Sprinkler (Final)7/1/20087/1/20087/1/2008 5:02:21 PMPFAIL
use approved fittings at service tie in.
PLM08-01555 Sprinkler (Final)6/30/20087/1/20087/1/2008 2:36:13 PMPFAIL
Peter Phone #: ###-#### need approved fittings at water service tie in
PLM08-01553 Sprinkler (Final)6/30/20087/1/20087/1/2008 2:22:43 PMPPASS
Peter Phone #: ###-####
PLM08-01552 Sprinkler (Final)6/30/20087/1/20087/1/2008 2:22:30 PMPPASS
Peter Phone #: ###-####
PLM08-01554 Sprinkler (Final)6/30/20087/1/20087/1/2008 2:22:13 PMPPASS
Peter Phone #: ###-####
PLM08-01297 Water and/or Sewer7/1/20087/1/20087/1/2008 2:04:55 PMPPART
Scheduled by a contractor via Hello! on 7/1/2008 at 11:12:58 AM. Contact: ###-####. water service ok
PLM08-00652 Final7/1/20087/1/20087/1/2008 1:27:31 PMPPASS
final ok
MEC08-01899 Rough-in6/30/20087/1/20087/1/2008 10:58:26 AMAPASS
Contact Lemmon Construction for access. ###-#### Phone #: ###-#### Internet Inspection Request from: Frank Marturello ri 20# test ok, will need to update existing water heater flue by final.
MEC08-01863 Final6/30/20087/1/20087/1/2008 10:10:27 AMAPASS
michaelle Phone #: ###-#### ri ok
MEC08-01849 Rough-in6/30/20087/1/20087/1/2008 9:37:45 AMAPASS
gas and ri reinspect Phone #: ###-#### Internet Inspection Request from: LINDA DORN ri 20# test ok
PLM08-01525 Final6/30/20087/1/20087/1/2008 9:10:25 AMAFAIL
Deloris Phone #: ###-#### pump water from around connection to water service. shut off and drain valves must be 36" below grade. 160 PSI min. PEX service piping required between service connection and backflow preventer. test backflow preventer.
PLM07-02062 Other7/1/20087/1/20087/1/2008 8:42:39 AMAPART
-can wasah correction notice.-
1)PVB is not listed for back pressure.
2) An R.P. is required on the water supply to the can wash and hose reel due to a direct connection to the inlet side of a sewer connected trap below the flood level rim, degree of hazard(garbage can wash) and elevated piping downstream of the backflow preventer.
PLM08-00998 Roof Drains6/30/20087/1/20086/30/2008 2:35:40 PMAPART
Please call Tim with any questions ###-#### Phone #: ###-#### Internet Inspection Request from: Sonja Hankel
PLM08-00998 Plumbing Rough-in6/30/20087/1/20086/30/2008 2:35:27 PMAPART
Please call Tim with any questions ###-#### Phone #: ###-#### Internet Inspection Request from: Sonja Hankel