Inspections for the day of: Tuesday, July 1, 2008.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00109 INSP-Final Inspection7/1/20087/1/20087/2/2008 9:12:52 AMPDEFR
Scheduled by a contractor via Hello! on 7/1/2008 at 7:55:22 AM. Contact: ###-####.
FIR08-00312 INSP-Final Inspection7/1/20087/1/20087/1/2008 4:14:08 PMPFAIL
NFPA 72 forms, letter of completion were not filled out. No testing performed on smoke detectors, contractor did not have canned smoke. sprinkler flow switch and tamper were tested. No other testing completed.KR
FIR08-00288 INSP-Final Inspection7/1/20087/1/20087/1/2008 4:06:36 PMPPASS
Fire sprinkler permit finaled.
FIR08-00393 INSP-Final Inspection7/1/20087/1/20087/1/2008 3:42:23 PMPPASS
Fire sprinkler final inspection passed, permit finaled.
FIR08-00182 INSP-Sprinkler Rough-in6/30/20087/1/20087/1/2008 3:32:15 PMPPART
UG fire supply line flush completed okay
BLD08-01113 FIRE-Final Inspection7/1/20087/1/20087/1/2008 3:31:09 PMPPASS
Fire life safety finaled.
FIR08-00376 INSP-Final Inspection7/1/20087/1/20087/1/2008 3:30:36 PMPPASS
Fire sprinkler permit finaled, one missing escutcheon installed while on site.
BLD08-01112 FIRE-Alarm Testing7/1/20087/1/20087/1/2008 2:04:09 PMPDONE
Duplicate inspection request.
BLD08-00197 FIRE-Final Inspection6/30/20087/1/20087/1/2008 2:02:56 PMAFAIL
Missing ceiling tile at several locations, need to repair one exit sign, one PFE is overdue annual certification at the server room, need to verify door mag locks drop out on fire alarm and power loss, not all items reviewed at this time, discussed subsequent permits for future remodel work.
BLD07-02689 FIRE-Final Inspection6/30/20087/1/20087/1/2008 1:58:44 PMAFAIL
Noted overspaced fire sprinkler heads, missing ceiling tile, one non-functional exit sign, locking hardware at several office slider doors is not approved, discussed general fire life safety requirements.
FIR08-00268 INSP-Final Inspection6/27/20087/1/20087/1/2008 11:44:54 AMAPASS
Fire alarm testing completed.3 Pull stations were to high. Pull stations were lower while I was on site testing sprinkler system.Retest pull stations. KR
FIR08-00300 INSP-Final Inspection6/30/20087/1/20087/1/2008 11:41:41 AMAPASS
Fire sprinkler hydro completed also final inspection. KR
BLD08-01113 FIRE-Alarm Testing6/30/20087/1/20087/1/2008 11:30:22 AMAPASS
Fire life safety inspection passed, one missing fire sprinkler escutcheon replaced while on site, noted project related fire sprinkler permit needs requested for final as well as correct inspection type called in for the BLD permit as "fire final" to ensure accurate documentation.
BLD08-00797 FIRE-Final Inspection7/1/20087/1/20087/1/2008 11:25:44 AMPFAIL
Fire extinguisher mounted to high, top of handle needs to be max 48" also needs cert tag. Address needs to be installed. All locking door handles need to be replaced with compliant handles. Dead bolt on back door needs to be removed. Need to install sign above main exit, door to remain unlocked while occupied.KR
FIR07-00902 INSP-Sprinkler Rough-in6/30/20087/1/20087/1/2008 11:24:42 AMAPART
Forward flow of the DCVA backflow preventer completed satisfactory.
BLD08-01112 FIRE-Conference6/30/20087/1/20087/1/2008 11:23:03 AMAFAIL
Need to repair two EM lights, exit door hardware at the east side exit is not approved, project related fire sprinkler permit needs to be requested for final, one PFE at the kitchen installed while on site, need to resolve plenum rated data cable issue.
FIR08-00210 INSP-Sprinkler Rough-in/Hydro6/27/20087/1/20087/1/2008 11:19:36 AMAFAIL
Overhead hydrostatic test failed due to start pressure below 200 psi. (guage @ 176 psi).
BLD07-03288 FIRE-Final Inspection7/1/20087/1/20087/1/2008 10:40:03 AMPPASS
Changes made per last inspection were completed.KR