FIR09-00084
| FIR-Aging Inspection | 7/1/2010 | 7/1/2010 | 7/6/2010 11:01:20 AM | | NR |
|
|
Per Bill the scheduling of all of the AES projects is being addressed.
|
FIR05-00727
| INSP-Conference | 6/10/2010 | 7/1/2010 | 7/2/2010 10:59:00 AM | A | DONE |
|
|
I left a message on Joan's voice mail at AIE ###-#### requesting job status.
|
FIR04-00376
| INSP-Conference | 6/9/2010 | 7/1/2010 | 7/2/2010 10:55:55 AM | A | DONE |
|
|
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
|
FIR03-00510
| INSP-Conference | 6/9/2010 | 7/1/2010 | 7/2/2010 10:55:38 AM | A | DONE |
|
|
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
|
FIR04-00375
| INSP-Conference | 6/9/2010 | 7/1/2010 | 7/2/2010 10:55:17 AM | A | DONE |
|
|
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
|
FIR04-00374
| INSP-Conference | 6/9/2010 | 7/1/2010 | 7/2/2010 10:54:54 AM | A | DONE |
|
|
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
|
FIR03-00381
| INSP-Conference | 6/9/2010 | 7/1/2010 | 7/2/2010 10:54:33 AM | A | DONE |
|
|
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
|
FIR10-00287
| INSP-Sprinkler Rough-in | 7/1/2010 | 7/1/2010 | 7/2/2010 9:41:07 AM | P | PASS |
|
|
Sprinkler piping rough-in passed. Still need a tenting inspection.
|
FIR10-00280
| INSP-Final Inspection | 6/30/2010 | 7/1/2010 | 7/1/2010 1:22:58 PM | A | CANC |
|
|
Inspection cancelled due to issues on the AES inspection on the building next door. Per the technician the activation of a supervisory signal will send a general alarm from the AES panel but a supervisory from the intella-tap. Both signals need to be a supervisory signal. This inspection will be rescheduled.
|
FIR10-00279
| INSP-Final Inspection | 6/30/2010 | 7/1/2010 | 7/1/2010 1:20:46 PM | A | FAIL |
|
|
The Netcon was a 5. Trouble and alarm signals went out. But the activation of a supervisory signal sent a general alarm from the AES panel but a supervisory from the intella-tap. Both signals need to be a supervisory signal.
|
BLD10-00555
| FIRE-Final Inspection | 6/30/2010 | 7/1/2010 | 7/1/2010 1:12:35 PM | A | PASS |
|
|
Life safety passed. Dixie approved the type II hood.
|
BLD10-00789
| FIRE-Final Inspection | 6/30/2010 | 7/1/2010 | 7/1/2010 10:06:41 AM | A | FAIL |
|
|
See the city approved plans for the deficiencies marked in red and dated with todays date. They include a missing exit sign/emergemcy light, current annal inspection tag for both fire extinguishers, panic hardware required at the main exit, single action hardware on both the restroom and storage room doors and missing occupant load signs.
|
BLD10-00998
| FIRE-Final Inspection | 6/30/2010 | 7/1/2010 | 7/1/2010 9:23:26 AM | A | PASS |
|
|
Life safety passed.
|