Inspections for the day of: Thursday, July 1, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00084 FIR-Aging Inspection7/1/20107/1/20107/6/2010 11:01:20 AM NR
Per Bill the scheduling of all of the AES projects is being addressed.
FIR05-00727 INSP-Conference6/10/20107/1/20107/2/2010 10:59:00 AMADONE
I left a message on Joan's voice mail at AIE ###-#### requesting job status.
FIR04-00376 INSP-Conference6/9/20107/1/20107/2/2010 10:55:55 AMADONE
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
FIR03-00510 INSP-Conference6/9/20107/1/20107/2/2010 10:55:38 AMADONE
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
FIR04-00375 INSP-Conference6/9/20107/1/20107/2/2010 10:55:17 AMADONE
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
FIR04-00374 INSP-Conference6/9/20107/1/20107/2/2010 10:54:54 AMADONE
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
FIR03-00381 INSP-Conference6/9/20107/1/20107/2/2010 10:54:33 AMADONE
Follow up with Bob at Oxard. Phone ###-#### #110. I left a message on Bob's voice mail requesting an updated job status
FIR10-00287 INSP-Sprinkler Rough-in7/1/20107/1/20107/2/2010 9:41:07 AMPPASS
Sprinkler piping rough-in passed. Still need a tenting inspection.
FIR10-00280 INSP-Final Inspection6/30/20107/1/20107/1/2010 1:22:58 PMACANC
Inspection cancelled due to issues on the AES inspection on the building next door. Per the technician the activation of a supervisory signal will send a general alarm from the AES panel but a supervisory from the intella-tap. Both signals need to be a supervisory signal. This inspection will be rescheduled.
FIR10-00279 INSP-Final Inspection6/30/20107/1/20107/1/2010 1:20:46 PMAFAIL
The Netcon was a 5. Trouble and alarm signals went out. But the activation of a supervisory signal sent a general alarm from the AES panel but a supervisory from the intella-tap. Both signals need to be a supervisory signal.
BLD10-00555 FIRE-Final Inspection6/30/20107/1/20107/1/2010 1:12:35 PMAPASS
Life safety passed. Dixie approved the type II hood.
BLD10-00789 FIRE-Final Inspection6/30/20107/1/20107/1/2010 10:06:41 AMAFAIL
See the city approved plans for the deficiencies marked in red and dated with todays date. They include a missing exit sign/emergemcy light, current annal inspection tag for both fire extinguishers, panic hardware required at the main exit, single action hardware on both the restroom and storage room doors and missing occupant load signs.
BLD10-00998 FIRE-Final Inspection6/30/20107/1/20107/1/2010 9:23:26 AMAPASS
Life safety passed.