Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00257 INSP-Sprinkler Rough-in/Hydro6/27/20136/28/2013 A 
7:AM requested. (discussed with Troy) Phone #: ###-#### >> Inspection requested via web by Jason Babien
BLD12-02063 FIRE-Final Inspection6/27/20136/28/2013 A 
Steve Phone #: ###-####
BLD12-01298 FIRE-Conference7/1/20137/1/20137/1/2013 3:50:20 PMPDONE
Greg and I went over life safety requirements for when an occupancy inspection is performed for a future tenant.
BLD12-01298 FIRE-Final Inspection7/1/20137/1/20137/1/2013 3:48:30 PMPPASS
Life safety passed. Fire dept access is from Orchard St. and the address has been posted.
BLD12-02045 FIRE-Final Inspection7/1/20137/1/20137/1/2013 3:46:51 PMPFAIL
Project was not quite ready for fire life safety but we verified all of the emergency light was funtional and found three light that did not work but two of which were repaired while I waited. We also went over fire dept access curb painting.
FIR13-00087 INSP-Final Inspection7/1/20137/1/20137/1/2013 3:44:27 PMPFAIL
Need as-builts showing the manual pull station at the entrance being relocated and the addition of a monitor module for the PIV. Also one hvac unit would not shut down under heat mode and the other hvac unit would not go into heat mode so that we could test the duct smoke detector. All other devices tested ok.
BLD13-00892 FIRE-Final Inspection7/1/20137/1/20137/1/2013 3:39:54 PMPPASS
life safety passed
FIR12-00670 INSP-Final Inspection6/28/20137/1/20137/1/2013 3:37:26 PMAPASS
Permit finaled
BLD12-02334 FIRE-Final Inspection7/1/20137/1/20137/1/2013 10:20:05 AMPPASS
Life safety passed.
BLD13-00890 FIRE-Final Inspection6/28/20137/1/20137/1/2013 10:00:57 AMAPASS
Life safety passed
FIR13-00239 INSP-Final Inspection6/28/20137/1/20137/1/2013 9:59:35 AMAPASS
Permit finaled
FIR13-00190 INSP-Final Inspection7/1/20137/1/20137/1/2013 9:58:28 AMPPASS
Permit finaled
FIR13-00190 INSP-Final Inspection7/1/20137/1/20137/1/2013 9:05:18 AMAFAIL
No access to the thermostat. Will come back later for the inspeciton scheduled for this afternnon.
BLD12-02334 FIRE-Final Inspection6/28/20137/1/20137/1/2013 8:23:04 AMAFAIL
Duct detector is missing the sample tubes and all of them are not wired to provide immediate shut down as required byIMC
FIR13-00280 INSP-Final Inspection7/1/20137/1/20137/1/2013 8:15:16 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Mark Scharfen Inspection cancelled from web by: Mark Scharfen