FIR13-00257
| INSP-Sprinkler Rough-in/Hydro | 6/27/2013 | 6/28/2013 | | A | |
|
|
7:AM requested. (discussed with Troy) Phone #: ###-#### >> Inspection requested via web by Jason Babien
|
BLD12-02063
| FIRE-Final Inspection | 6/27/2013 | 6/28/2013 | | A | |
|
|
Steve Phone #: ###-####
|
BLD12-01298
| FIRE-Conference | 7/1/2013 | 7/1/2013 | 7/1/2013 3:50:20 PM | P | DONE |
|
|
Greg and I went over life safety requirements for when an occupancy inspection is performed for a future tenant.
|
BLD12-01298
| FIRE-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 3:48:30 PM | P | PASS |
|
|
Life safety passed. Fire dept access is from Orchard St. and the address has been posted.
|
BLD12-02045
| FIRE-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 3:46:51 PM | P | FAIL |
|
|
Project was not quite ready for fire life safety but we verified all of the emergency light was funtional and found three light that did not work but two of which were repaired while I waited. We also went over fire dept access curb painting.
|
FIR13-00087
| INSP-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 3:44:27 PM | P | FAIL |
|
|
Need as-builts showing the manual pull station at the entrance being relocated and the addition of a monitor module for the PIV. Also one hvac unit would not shut down under heat mode and the other hvac unit would not go into heat mode so that we could test the duct smoke detector. All other devices tested ok.
|
BLD13-00892
| FIRE-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 3:39:54 PM | P | PASS |
|
|
life safety passed
|
FIR12-00670
| INSP-Final Inspection | 6/28/2013 | 7/1/2013 | 7/1/2013 3:37:26 PM | A | PASS |
|
|
Permit finaled
|
BLD12-02334
| FIRE-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 10:20:05 AM | P | PASS |
|
|
Life safety passed.
|
BLD13-00890
| FIRE-Final Inspection | 6/28/2013 | 7/1/2013 | 7/1/2013 10:00:57 AM | A | PASS |
|
|
Life safety passed
|
FIR13-00239
| INSP-Final Inspection | 6/28/2013 | 7/1/2013 | 7/1/2013 9:59:35 AM | A | PASS |
|
|
Permit finaled
|
FIR13-00190
| INSP-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 9:58:28 AM | P | PASS |
|
|
Permit finaled
|
FIR13-00190
| INSP-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 9:05:18 AM | A | FAIL |
|
|
No access to the thermostat. Will come back later for the inspeciton scheduled for this afternnon.
|
BLD12-02334
| FIRE-Final Inspection | 6/28/2013 | 7/1/2013 | 7/1/2013 8:23:04 AM | A | FAIL |
|
|
Duct detector is missing the sample tubes and all of them are not wired to provide immediate shut down as required byIMC
|
FIR13-00280
| INSP-Final Inspection | 7/1/2013 | 7/1/2013 | 7/1/2013 8:15:16 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Mark Scharfen Inspection cancelled from web by: Mark Scharfen
|