Inspections for the day of: Tuesday, July 1, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01678 ELE-Aging Inspection7/1/20147/1/20147/7/2014 3:19:52 PM DONE
left message
ELE12-01956 ELE-Aging Inspection7/1/20147/1/20147/3/2014 10:49:27 AM DONE
too busy
ELE14-01757 Electrical Rough-In6/30/20147/1/20147/1/2014 2:44:28 PMAFAIL
PLEASE GIVE AN HOUR NOTICE PRIOR TO INSPECTION FOR ACCESS TO HOME. THANK YOU. Phone #: ###-#### >> Inspection requested via web by Kendra Lanham 11/4" to nm cable at a few locations needed,
ELE14-00990 Final6/30/20147/1/20147/1/2014 1:13:05 PMAPASS
Warren Phone #: ###-#### final ok
ELE14-01766 Rough-In Permanent Service7/1/20147/1/20147/1/2014 12:39:21 PMACANC
call first Phone #: ###-#### >> Inspection requested via web by PAT MILLER needed p/s
ELE14-01766 Permanent Service7/1/20147/1/20147/1/2014 12:38:27 PMPPASS
call first Phone #: ###-#### >> Inspection requested via web by PAT MILLER p/s o/h rec ok
ELE14-01712 Electrical Rough-In6/30/20147/1/20147/1/2014 12:13:01 PMAPASS
If you have any questions, please call Jake ###-####. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan r/i ok
ELE14-01759 Final6/30/20147/1/20147/1/2014 11:55:33 AMAFAIL
Access code is 0475. Phone #: ###-#### >> Inspection requested via web by Paula Gratiot current panel schedule needed, exposed 120 splice to doorbell x-former, fused nuetral in furnace disconnect, no GFCI protection in bathroom and kitchen countertop plugmold and no ground, in use cover on front exterior GFCI receptacle, basement receptacles have reverse polarity and not GFCI protected within 6 ' of sink, blank plate on ceiling box at bottom of stairs
ELE14-01284 Electrical Rough-In7/1/20147/1/20147/1/2014 10:43:21 AMAFAIL
Rough-in of addition. Phone #: ###-#### >> Inspection requested via web by Steve Craig 400.8 (2) flexable cords not permitted where concealed in walls ,floors or ceilings. 336.12(2) where installed outside raceway or cable tray..
ELE14-01667 Electrical Rough-In6/30/20147/1/20147/1/2014 9:30:18 AMACANC
Matt Phone #: ###-#### >> Inspection requested via web by Sean DeLacy needed conf
ELE14-01667 Conference7/1/20147/1/20147/1/2014 9:26:18 AMPDONE
Matt Phone #: ###-#### >> Inspection requested via web by Sean DeLacy not ready for r/i discuss mini split system wiring
ELE13-02057 Electrical Rough-In6/30/20147/1/20147/1/2014 8:40:34 AMAPASS
Ticket booth underground. Robert is the on-site contact. Phone #: ###-#### >> Inspection requested via web by Buster Bowen r/i u.g. ok