Inspections for the day of: Tuesday, July 1, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00440 INSP-Final Inspection7/1/20147/1/20147/1/2014 5:05:45 PMPPART
Inspection for scope of work at the basement level. Discussed seismic bracing, standard response heads, pump layout, added and relocated sprinkler coverage.
FIR14-00387 INSP-Final Inspection6/30/20147/1/20147/1/2014 5:03:33 PMAPASS
Fire sprinkler permit finaled.
BLD14-00664 FIRE-Final Inspection6/30/20147/1/20147/1/2014 1:14:55 PMAPASS
Verified previous correction items are finished. Fire life safety finaled.
BLD14-01271 FIRE-Final Inspection6/30/20147/1/20147/1/2014 1:13:28 PMAPASS
Fire life safety passed. Batteries at three exit signs repaired while on site.
FIR14-00277 INSP-Sprinkler Rough-in6/30/20147/1/20147/1/2014 1:11:41 PMAPART
Okay to cover remainder of UG fire supply line including remote FDC piping. Need to provide seismic clearance method at the ductile riser, wrap galvanized FDC stub.
BLD14-01371 FIRE-Final Inspection6/30/20147/1/20147/1/2014 1:08:54 PMAPASS
Plans need revised to show scope of work completed, refer to plan keynote item #7. Remainder of fire life safety inspection passed. Plan mod to be done prior to structural final as discussed.
FIR14-00375 INSP-Sprinkler Rough-in6/30/20147/1/20147/1/2014 1:05:55 PMAPART
Overhead rough-in inspection completed. Need to install missing coverage at a closet and provide head per plan review comments at the fireplace.
FIR14-00368 INSP-Sprinkler Rough-in6/30/20147/1/20147/1/2014 1:02:30 PMAPART
Overhead rough-in for branchlines and armovers at the new pharmacy area drop and sheetrock lid ceilings passed inspection. *Drops and grid work not yet installed. Plans dated and initialed.
BLD14-01847 FIRE-Final Inspection6/30/20147/1/20147/1/2014 12:59:06 PMAPASS
Life safety inspection completed satisfactory. Signature card not available on site.
FIR14-00387 INSP-Final Inspection6/30/20147/1/20146/30/2014 3:14:22 PMACANC
This is a rough in & final. Stefan is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus