Inspections for the day of: Monday, July 1, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS19-00187 MEC-Final7/1/20197/1/20197/2/2019 12:55:30 PMPFAIL
Jerad Phone #: ###-####
-Need to have engineered drawings from an Idaho licensed engineer for mechanical ventilation of site operations which include painting, welding, and cutting shipping containers. Drawings will then need to be submitted to the City of Boise for approval
MEC19-00971 Final7/1/20197/1/20197/1/2019 3:53:12 PMPPASS
Chilled loop has been insulated and labeled and connected to owner provided chiller. Phone #: ###-#### Inspection requested via web by Travis Baker
- final ok
- sign occ card
MEC19-01262 Final6/25/20197/1/20197/1/2019 3:31:49 PMPPASS
Please call ahead to Dana ###-####. Phone #: ###-#### Inspection requested via web by Whitney Newsom
- final ok
MEC19-02542 Final7/1/20197/1/20197/1/2019 3:06:12 PMPPASS
Call homeowner 30min ahead ###-####
- A/C coil co ok
MEC19-02834 Final7/1/20197/1/20197/1/2019 2:50:16 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- A/C coil co ok
MEC19-01471 Final6/27/20197/1/20197/1/2019 2:34:59 PMPPASS
entry code should be 1271 or 1217 or 6997 Phone #: ###-#### Inspection requested via web by Angie Maguire
- final ok
MEC19-02655 Final6/24/20197/1/20197/1/2019 2:03:39 PMPPASS
Homeowner Carissa Bafford ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-00795 Rough-in7/1/20197/1/20197/1/2019 1:45:02 PMPNH
call for acess- late afternoon- Milorad Phone #: ###-####
- called number in notes and no answer
- no access to home left notice on front door
MEC19-02692 Rough-in7/1/20197/1/20197/1/2019 1:24:44 PMPPASS
Call James at ###-#### with any questions, thanks. Inspection requested via web by 4 Seasons
- R/I ok
MEC19-00581 Rough-in6/28/20197/1/20197/1/2019 11:00:13 AMAPART
Requesting an R/I inspection for the Mechanical Room on 7-1-19. Please call Mark before coming out - ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
- duct work in mech room ok
- need to see pool heater install instructions for venting
- b vent for pool heater needs 1" to combustibles and one location needs clearance reduction installed
- mech room needs damper signage installed on wall for final
- access doors need installed in ceiling for hvac zones
MEC19-02799 Final6/28/20197/1/20197/1/2019 9:44:10 AMAPASS
call Amy before coming Phone #: ###-#### Inspection requested via web by Kim Lithander
- A/C coil co ok
MEC19-02797 Pressure Test6/28/20197/1/20197/1/2019 9:23:23 AMAPASS
Pressure Test
Please call Lance Manning w/questions. ###-#### Phone #: ###-#### Inspection requested via web by PATTY KIRK
- 60lb undergound gas pressure test ok
- ok for backfill
- tagged new gas line
MEC19-02329 Final6/27/20197/1/20197/1/2019 9:13:28 AMAFAIL
Please call Bill in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout
- need to see co detector near bedrooms
- A/C fuses need to be 25amp
MEC19-02817 Final6/28/20197/1/20197/1/2019 9:01:27 AMAPASS
PLEASE CALL TENANT BECKY @ # LISTED WHEN EN ROUTE Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
- air handler coil only ok
MEC18-05316 Final6/28/20197/1/20197/1/2019 8:44:31 AMAPASS
David ###-####
CODE: 7060 Phone #: ###-#### Inspection requested via web by Mike Almanza
- fireplace final ok
MEC18-03329 Mec-Aging Inspection7/1/20197/1/20197/1/2019 8:12:25 AM PASS
permit expired ok
MEC18-03329 DOC - Permit Expired7/1/20197/1/20197/1/2019 8:12:06 AMAPASS
permit expired ok