Inspections for the day of: Wednesday, July 10, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02084 Temporary Service7/9/20027/10/20027/10/2002 12:00:00 AMACANC
kevin ###-####
ELE02-02036 Rough-In Permanent Service7/9/20027/10/20027/10/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 07/09/2002 at 11:45:28. Contact: ###-####. corrections not made called 7/10/2002 2:24:54 PM
ELE02-01291 Final7/9/20027/10/20027/10/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 07/09/2002 at 14:19:35. Contact: ###-####. cor. posted called 110.14 copper and alum under small splice 406.4 recepts not secure, and set back in plates, welding cable not approved for installation in wireway or raceway, install all covers on wireway and provide bushing where x-ray cables exit covers call Jack for more info 7/10/2002 5:44:47 PM
ELE02-01820 Permanent Service7/9/20027/10/20027/10/2002 12:00:00 AMAPART
ufer ground ###-#### ok for concrete cover 7/10/2002 10:09:56 AM
ELE02-01032 Electrical Rough-In7/9/20027/10/20027/10/2002 12:00:00 AMAPART
CONFERENCE ###-#### BRAD ok correction posted needs clearence above panelboards basement remove pipes from above panels 7/10/2002 11:19:09 AM
ELE02-00775 Final7/10/20027/10/20027/10/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 07/10/2002 at 07:04:30. Contact: ###-####. temp occupancy ok sign contractor needs permit 7/10/2002 10:20:15 AM
ELE02-02052 Electrical Rough-In7/10/20027/10/20027/10/2002 12:00:00 AMPFAIL
kevin ###-#### corrections not made called 7/10/2002 2:44:24 PM
ELE01-03982 Final7/10/20027/10/20027/10/2002 12:00:00 AMPPASS
###-#### ok 7/10/2002 5:45:01 PM
ELE02-02093 Electrical Rough-In7/10/20027/10/20027/10/2002 12:00:00 AMPNR
###-#### called needs recept within 25 ft 7/10/2002 6:43:25 PM
ELE02-01889 Electrical Rough-In7/10/20027/10/20027/10/2002 12:00:00 AMPNH
DAVID ###-#### PLEASE CALL DAVID SO HE CAN UNLOCK THE DOOR.. called no one there, stopped at job site no access 7/11/2002 11:17:56 AM