Inspections for the day of: Thursday, July 10, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00132 FIR-Aging Inspection7/10/20037/10/20037/10/2003 12:00:00 AM FAIL
I spoke with Jim Danes with debest fire and we agreed to perform this inspection when FIR03-00349 is ready to be inspected 7/10/2003 8:59:54 AM
FIR02-00226 INSP-Final Inspection7/9/20037/10/20037/10/2003 12:00:00 AMACANC
Contractor, Patrick w/Protex, called and said that there were no approved drawings on site. He will reschedule 7/10/2003 12:40:47 PM
BLD03-00035 FIRE-Final Inspection7/9/20037/10/20037/10/2003 12:00:00 AMAFAIL
duct smoke detectors in Block Buster do not shut down the hvac units 7/10/2003 8:53:11 AM
FIR03-00134 INSP-Conference7/9/20037/10/20037/10/2003 12:00:00 AMAPASS
Inspection was for the hydro test on the underground supply. Hydro test is OK 7/10/2003 9:29:27 AM
FIR02-00311 INSP-Sprinkler Rough-in/Hydro7/10/20037/10/20037/10/2003 12:00:00 AMPPART
conference room in the northwest corner of the building is ok to cover. One pendant is not installed per plan. The sprinkler fitter said he would correct it. Its location is marked on the plans and will be checked on the next inspection 7/10/2003 2:19:01 PM
FIR02-00459 INSP-Sprinkler Rough-in/Hydro7/10/20037/10/20037/10/2003 12:00:00 AMPPART
All rough-in ok except for 12 more pendants that need cut in 7/10/2003 4:04:18 PM
BLD03-00035 FIRE-Final Inspection7/10/20037/10/20037/10/2003 12:00:00 AMPPASS
fire life safety for the shell and core finaled 7/10/2003 2:41:30 PM