Inspections for the day of: Monday, July 10, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00301 ELE-Aging Inspection7/10/20067/10/20067/10/2006 4:30:42 PM NR
checked with contr, should be getting closer for final
ELE06-00703 Final7/10/20067/10/20067/10/2006 4:29:04 PMPPASS
Scheduled by a contractor via Hello! on 7/10/2006 at 10:07:00 AM. Contact: ###-####. corr made, ok to final
ELE06-02528 Final7/10/20067/10/20067/10/2006 3:36:08 PMPPASS
chuck - #53; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE05-00855 ELE-Aging Inspection7/10/20067/10/20067/10/2006 2:28:56 PM DONE
suc
ELE06-00319 Electrical Rough-In7/10/20067/10/20067/10/2006 2:27:56 PMPPART
JENNIE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover out side perimeter walls only around office areas
ELE06-02155 Rough-In Permanent Service7/7/20067/10/20067/10/2006 1:07:15 PMPPART
underground for service to pool area thyere will be a service change done permit has been changed thanks joe; Phone #: ###-#### Internet Inspection Request from: joe wheeler called contr to ensure 18" depth where mud sluffed in. ok to cover u/g from service area to pool area only
ELE06-02501 Rough-In Permanent Service7/6/20067/10/20067/10/2006 11:05:51 AMANR
brandon; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left message, too many things not ready,garage not done,front lite boxes,lv in line voltage raceways, 1 1/4" holes and cable, nm stapled on edges, subpanel cable not strapped, wrong clamp for same, bath fixtures missing, stair fixt missing, tub not ready, too many nm cables under staples, said to call when ready
ELE06-00703 Final7/7/20067/10/20067/10/2006 10:07:10 AMAFAIL
Scheduled by a contractor via Hello! on 7/7/2006 at 5:39:58 PM. Contact: ###-####. told elect, left corr notice, 210.52(D) recpt shall be within 3' 0f basin in mbr, 422.16(B)(2) disposal cord shall not be over 36", 406.4(D) recpt faceplate shall be flush or project from recpt face, 408.4 panelboard schedule shall be complete and accurate
ELE06-01369 Final7/7/20067/10/20067/10/2006 9:53:56 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: William Zerfas called left message left corr notice, nec 210.8(A)(6) kitchen recpts shall be gfci protected, BCC microwave recpt shall be completed
ELE06-01627 Permanent Service7/7/20067/10/20067/10/2006 9:35:50 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton p/s u/g n ok
ELE06-02496 Rough-In Permanent Service7/10/20067/10/20067/10/2006 9:19:54 AMAPART
Scheduled by a contractor via Hello! on 7/10/2006 at 5:33:07 AM. Contact: ###-####. p/s u/g n ok, called on ri, nec 300.4(D) nm cable shall be 1 1/4" from edge of framing member,314.20 boxes shall be flush in walls of combustible material, 210.52(A) shall add recpt to 2' wall by hall to bedrooms, BCC all make-up shall be done
ELE06-02247 Final7/7/20067/10/20067/10/2006 8:46:43 AMANH
final on 1 room addition, back door will be open okay to go in, house is vacant. any questions call Tate @ ###-#### Internet Inspection Request from: Andy Rose 2nd time no acess,called ,fee due
ELE06-02497 Rough-In Permanent Service7/10/20067/10/20067/10/2006 8:41:50 AMAPASS
Scheduled by a contractor via Hello! on 7/10/2006 at 5:35:30 AM. Contact: ###-####. ric ok, p/s u/g n ok
ELE06-02160 Electrical Rough-In7/10/20067/10/20067/10/2006 8:09:37 AMAFAIL
Scheduled by a contractor via Hello! on 7/10/2006 at 6:00:06 AM. Contact: ###-####. called, left message, BCC equipotential plane shall be on blocks ready to pour