Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00790 FIRE-Final Inspection7/10/20067/10/20067/10/2006 4:30:05 PMACANC
Wrong inspector for inspection
FIR05-00800 INSP-Final Inspection7/10/20067/10/20067/10/2006 4:28:14 PMPPART
The second floor portion of the fire alarm system is passed. Still need to test the connection between the new NAC and the main FACP.
FIR06-00246 INSP-Alarm Testing7/10/20067/10/20067/10/2006 4:26:20 PMPFAIL
No test performed due to ehen the manual pull station in the basement was pulled not a/v's went off. The pull station that was tested did not corrispond with the assigned address on the plans. Also the a/v in the kitchen needs to be relocated as discussed due to blockage by duct work. All other a/v's appear to be located correctly. No other testing was done.
FIR05-00588 INSP-Final Inspection7/7/20067/10/20067/10/2006 4:18:49 PMAFAIL
Provide map at the facp, fix the pone line one and phone line two reporting, outside alarm bell can not be silenced by the facp and provide atleast 8.3 ah battery for the facp.
BLD05-02073 FIRE-Final Inspection7/7/20067/10/20067/10/2006 12:57:37 PMAPART
The second floor only is ok to occupy.