BLD07-00343
| FIRE-Final Inspection | 7/10/2007 | 7/10/2007 | 7/11/2007 12:20:26 PM | A | FAIL |
|
|
Missing one exit sign at the north side stairway door.
|
BLD07-00343
| FIRE-Alarm Testing | 7/10/2007 | 7/10/2007 | 7/11/2007 12:19:23 PM | A | PART |
|
|
Alarm testing completed.
|
FIR07-00481
| INSP-Sprinkler Rough-in | 7/9/2007 | 7/10/2007 | 7/10/2007 3:56:17 PM | P | PART |
|
|
OH rough-in inspection completed okay, good for cover at the basement level only, the first floor has two locations where tenting is not adequate.
|
FIR07-00448
| INSP-Supply line flush | 7/9/2007 | 7/10/2007 | 7/10/2007 3:27:32 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory, hydrostatic test not ready due to pressure loss at the guage.
|
FIR07-00208
| INSP-Final Inspection | 7/9/2007 | 7/10/2007 | 7/10/2007 2:30:02 PM | A | FAIL |
|
|
Per fire code review notes items 2 and 5, need record of inspection and testing completed prior to final, supervisory signals shall be self restoring, missing lock at the FACP breaker, provide means to test phase reversal at the pump.
|
FIR07-00234
| INSP-Sprinkler Rough-in/Hydro | 7/9/2007 | 7/10/2007 | 7/10/2007 1:33:24 PM | A | FAIL |
|
|
Per requirements of IFC 2003 903.3.1.2.1 sprinkler protection shall be provided for exterior balconies and ground floor patios of dwelling units protected by a 13R system. The overhead hydrostatic testing for building 2 completed satisfactory.
|
BLD07-00824
| FIRE-Final Inspection | 7/9/2007 | 7/10/2007 | 7/10/2007 11:40:38 AM | A | NR |
|
|
Need the project related fire sprinkler permit finaled, also missing doors, ceilling tile, etc., project is not ready for life safety final at this time.
|
FIR07-00313
| INSP-Final Inspection | 7/10/2007 | 7/10/2007 | 7/10/2007 11:38:18 AM | A | PASS |
|
|
c/n items are finished, fire alarm passed final inspection, permit finaled.
|
FIR07-00453
| INSP-Final Inspection | 7/9/2007 | 7/10/2007 | 7/10/2007 11:36:55 AM | A | PASS |
|
|
Corrections verified for completion, fire sprinkler permit finaled.
|