BLD08-00277
| FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 3:50:12 PM | P | FAIL |
|
|
No approved city plan on site, egress lights at front and back entrances did not function and front door hardware was in correct.KR
|
FIR08-00338
| INSP-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 3:33:03 PM | P | PASS |
|
|
Fire alarm testing completed.KR
|
BLD07-01884
| FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 12:54:37 PM | A | FAIL |
|
|
Sprinkler plans are not finaled. Fire extinguisher in warehouse and truck shop need to be 4A, wrong extiguishers were installed. Fire extinguishers in offices need to be hung, Egress lighting at all exit from office spaces were not installed and misc emergency lights did not function. All egeress and emergency lights need to be retested.KR
|
FIR07-00935
| INSP-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 12:47:51 PM | A | FAIL |
|
|
Plans are still under review for resubmittals.Fire sprinkler Inspection completed. One remaining item.Chain and lock is required on PIV. KR
|
FIR08-00421
| INSP-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 11:56:15 AM | A | PASS |
|
|
Fire alarm testing complete. KR
|
FIR08-00178
| INSP-Sprinkler Rough-in | 7/9/2008 | 7/10/2008 | 7/10/2008 11:26:00 AM | A | PART |
|
|
The remainder of overhead fire sprinkler system modifications are approved for cover at the drop ceilings throughout the remodel area.
|
FIR06-00782
| INSP-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 11:03:50 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD08-00659
| FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 10:38:55 AM | A | PART |
|
|
Fire life safety final pending door hardware at the main level second exit door and extension of the existing building fire alarm system to include notification throughout the tenant space.
|
BLD06-01994
| FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 9:58:25 AM | A | PASS |
|
|
Fire life safety final inspection passed, correction notice items are finished.
|
BLD06-01992
| FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 9:57:14 AM | A | PASS |
|
|
C/N items verified for compliance, fire life safety final inspection passed.
|
BLD08-00345
| FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 9:55:05 AM | A | PASS |
|
|
Life safety inspection passed, one fire extinguisher due certification to be completed today per discussion with Richard of Colliers Int.
|
FIR08-00369
| INSP-Supply line flush | 7/7/2008 | 7/10/2008 | 7/10/2008 9:52:49 AM | A | PART |
|
|
UG fire supply line flush completed acceptable.
|
MIS06-00075
| FIR-Final | 7/7/2008 | 7/10/2008 | 7/10/2008 9:04:13 AM | A | PASS |
|
|
Door hardware changed, New sign added above door and fire extinguishers were lowered to correct height. KR
|
BLD00-00081
| FIRE-Conference | 7/10/2008 | 7/10/2008 | 7/10/2008 12:00:00 AM | P | DONE |
|
|
Per Forrest France's e-mail see scanned and attached documents- ok to doc final for Fire///7-10-08 BAS
|