Inspections for the day of: Thursday, July 10, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00277 FIRE-Final Inspection7/9/20087/10/20087/10/2008 3:50:12 PMPFAIL
No approved city plan on site, egress lights at front and back entrances did not function and front door hardware was in correct.KR
FIR08-00338 INSP-Final Inspection7/9/20087/10/20087/10/2008 3:33:03 PMPPASS
Fire alarm testing completed.KR
BLD07-01884 FIRE-Final Inspection7/9/20087/10/20087/10/2008 12:54:37 PMAFAIL
Sprinkler plans are not finaled. Fire extinguisher in warehouse and truck shop need to be 4A, wrong extiguishers were installed. Fire extinguishers in offices need to be hung, Egress lighting at all exit from office spaces were not installed and misc emergency lights did not function. All egeress and emergency lights need to be retested.KR
FIR07-00935 INSP-Final Inspection7/9/20087/10/20087/10/2008 12:47:51 PMAFAIL
Plans are still under review for resubmittals.Fire sprinkler Inspection completed. One remaining item.Chain and lock is required on PIV. KR
FIR08-00421 INSP-Final Inspection7/9/20087/10/20087/10/2008 11:56:15 AMAPASS
Fire alarm testing complete. KR
FIR08-00178 INSP-Sprinkler Rough-in7/9/20087/10/20087/10/2008 11:26:00 AMAPART
The remainder of overhead fire sprinkler system modifications are approved for cover at the drop ceilings throughout the remodel area.
FIR06-00782 INSP-Final Inspection7/9/20087/10/20087/10/2008 11:03:50 AMPPASS
Fire sprinkler permit finaled.
BLD08-00659 FIRE-Final Inspection7/9/20087/10/20087/10/2008 10:38:55 AMAPART
Fire life safety final pending door hardware at the main level second exit door and extension of the existing building fire alarm system to include notification throughout the tenant space.
BLD06-01994 FIRE-Final Inspection7/9/20087/10/20087/10/2008 9:58:25 AMAPASS
Fire life safety final inspection passed, correction notice items are finished.
BLD06-01992 FIRE-Final Inspection7/9/20087/10/20087/10/2008 9:57:14 AMAPASS
C/N items verified for compliance, fire life safety final inspection passed.
BLD08-00345 FIRE-Final Inspection7/9/20087/10/20087/10/2008 9:55:05 AMAPASS
Life safety inspection passed, one fire extinguisher due certification to be completed today per discussion with Richard of Colliers Int.
FIR08-00369 INSP-Supply line flush7/7/20087/10/20087/10/2008 9:52:49 AMAPART
UG fire supply line flush completed acceptable.
MIS06-00075 FIR-Final7/7/20087/10/20087/10/2008 9:04:13 AMAPASS
Door hardware changed, New sign added above door and fire extinguishers were lowered to correct height. KR
BLD00-00081 FIRE-Conference7/10/20087/10/20087/10/2008 12:00:00 AMPDONE
Per Forrest France's e-mail see scanned and attached documents- ok to doc final for Fire///7-10-08 BAS