BLD13-00938
| FIRE-Final Inspection | 7/8/2014 | 7/10/2014 | 7/11/2014 6:23:45 PM | A | PART |
|
|
2nd floor core area passed fire life safety inspection.
|
FIR13-00409
| INSP-Final Inspection | 7/10/2014 | 7/10/2014 | 7/10/2014 4:38:21 PM | P | PART |
|
|
Completed initial walkthrough at core areas. Identified adjustments to be made at some locations.
|
FIR14-00260
| INSP-Sprinkler Rough-in | 7/9/2014 | 7/10/2014 | 7/10/2014 4:36:19 PM | A | PART |
|
|
Branch line rough-in to drop outlets passed inspection.
|
FIR14-00196
| INSP-Sprinkler Rough-in/Hydro | 7/9/2014 | 7/10/2014 | 7/10/2014 12:00:43 PM | A | PART |
|
|
Previous correction items verified for completion including the riser, coverage at the fireplace, and tenting. Plan modification approval pending for changed pipe sizes, relocated branchlines, heads, etc.- okayed for cover conditional upon plan revision.
|
FIR14-00375
| INSP-Sprinkler Rough-in | 7/9/2014 | 7/10/2014 | 7/10/2014 11:56:06 AM | A | FAIL |
|
|
A newly added closet has blocked fire sprinkler coverage adjacent to the nook and kitchen areas, tenting is not adequate at two locations including a bedroom and the riser piece to the great room. Previous correction items are finished. Cover is not approved at this time.
|
FIR14-00375
| INSP-Supply line flush | 7/9/2014 | 7/10/2014 | 7/10/2014 11:51:43 AM | A | PART |
|
|
UG fire supply line flush completed acceptable.
|
BLD06-02323
| FIRE-Final Inspection | 7/9/2014 | 7/10/2014 | 7/10/2014 11:50:41 AM | A | PART |
|
|
Fire life safety inspection passed for unit 207 building #2.
|
BLD14-01850
| FIRE-Final Inspection | 7/9/2014 | 7/10/2014 | 7/10/2014 11:49:17 AM | A | PASS |
|
|
Life safety passed provided the fire extinguisher is mounted and tagged with a current certification prior to structural final as discussed.
|