ELE19-01687
| Final | 7/10/2019 | 7/10/2019 | 7/11/2019 10:19:10 AM | P | PEND |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen 110.12(B)- Equipment shall not be damaged. In ground junction box damaged on center light pole. 352.46- Where a conduit enters a box or enclosure a bushing or adapter shall be installed to protect conductors from damage. All in ground boxes. I checked wrong location on 7-10-19. Actual location installation complete and all good.
|
ELE19-02539
| Rough-In Permanent Service | 7/9/2019 | 7/10/2019 | 7/10/2019 2:50:23 PM | A | PASS |
|
|
Please contact when done Phone #: ###-#### Inspection requested via web by Thomas wilson 408.40- Each grounded conductor shall terminate in an individual terminal that is not used for another conductor. Ground and neutral terminated under single terminal, must correct by final. Underground rough in ok cover p/s u/g rec ok
|
ELE19-02369
| Final | 7/8/2019 | 7/10/2019 | 7/10/2019 2:11:04 PM | A | FAIL |
|
|
Please call Troy before heading that way, he works from home. The tech for this job is Brodie, please call with any questions ###-####. Phone #: ###-#### Inspection requested via web by William Salts Owner Troy ###-####. Panel located in a room that has been turned into a closet with shelf below and above panel and clothes rod installed. 110.26- Minimum work space of 30" wid and 36" deep shall be provided for panel. 240.24- Over current devices shall not be installed near easily igniteable materials such as clothes closets. Called and informed owner BLD13-00796 for the living space in garage had expired and to contact Bob Archibald to have permit reopened and then schedule BLD final once passed for occupancy would be able to request final on new ELE for mini-split. No inspection allowed until BLD final complete. Closet will need to be gutted completely to pass ELE final.
|
ELE19-01548
| Final | 7/9/2019 | 7/10/2019 | 7/10/2019 1:48:55 PM | A | PASS |
|
|
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|
ELE19-02504
| Electrical Rough-In | 7/9/2019 | 7/10/2019 | 7/10/2019 12:20:20 PM | A | PASS |
|
|
Please call Juan with any questions Phone #: ###-#### Inspection requested via web by William Salts Rough in ok cover
|
ELE19-02323
| Rough-In Permanent Service | 7/10/2019 | 7/10/2019 | 7/10/2019 11:30:18 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 110.3- Expansion joint shall be installed as per manufacturers instructions. At time of install joint shall be opened to mid point to allow for expansion and contraction. 110.14- Connection to concrete encased electode shall be tight. moved with fingers. 250.148- Metal boxes shall be connected to equipment grounding conductors. All equipment grounding conductors in a box shall be connected together. Complete make up. 300.15- All NM cables shall terminate in a box. Up bed smoke detector. 312.5(A)- Unused openings in meter base shall be closed by approved means. 2" KO open. 590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protection. 250 in temp pole failed test.
|
ELE19-02322
| Rough-In Permanent Service | 7/10/2019 | 7/10/2019 | 7/10/2019 11:20:08 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 110.3- Expansion joint shall be installed as per manufacturers instructions. At time of installation joint shall be expanded to mid point to allow for expansion and contraction. 110.14- Connection to concrete encased electrode shall be tight. Loose turned with fingers. 210.52- Wall spaces 24" and wider shall have receptacle outlets installed. Up bed switch wall. 250.148- All metal boxes shall be connected to equipment grounding conductors. All equipment grounding conductors in a box shall be connected together. Complete make up. 250.68(A)- Access shall be provided to connection to concrete encased electrode. Mud ring 8" above.
|
ELE19-01813
| Electrical Rough-In | 7/10/2019 | 7/10/2019 | 7/10/2019 10:07:30 AM | A | PASS |
|
|
FLOOR HEAT IN MASTER BATH INSPECTION Phone #: ###-#### Inspection requested via web by Bob Glenn Area noted rough in ok cover
|
ELE19-02500
| Rough-In Permanent Service | 7/9/2019 | 7/10/2019 | 7/10/2019 9:52:26 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE19-01317
| Final | 7/9/2019 | 7/10/2019 | 7/10/2019 9:24:25 AM | A | FAIL |
|
|
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden 210.12- All outlets located in bedrooms shall have AFCI protection. Smokes, switches and receptacles. 406.12- All 15 and 20 120 volt receptacle outlets installed in a dwelling unit shall be tamper resistant type. 422.30- All hardwired appliances shall have a disconnecting means. 110.25 lock outs acceptacle. Hood.
|