FIR20-00232
| INSP-Final Inspection | 7/9/2020 | 7/10/2020 | 7/10/2020 10:47:24 AM | A | FAIL |
|
|
Occupant notification appliances in sleeping areas of north wing required to be low frequency sounders. Heat detector in north wing bathroom needs to be replaced and retested due to damage to device. Heat detectors in attic space are restorable and means for testing are required for next inspection.
Device map/print to be provided at FACP.
Randy - /*Screened*/ Phone #: ###-####
|
FIR20-00084
| INSP-Final Inspection | 7/10/2020 | 7/10/2020 | 7/10/2020 10:45:39 AM | A | PASS |
|
|
Fire sprinkler passed and finaled. Flow switch, tampers and PS in riser room tested. Interior and exterior sprinkler heads and escutchions inspected. Required signage, replacement heads and documentation in place in riser room.
Please Call Brian Flechs at ###-#### about 30 minutes prior to heading to job site. He will be coming from the office to meet you onsite and it will take him about 30 minutes to get there. Phone #: ###-#### Inspection requested via web by Matt Barnard
|