FIR03-00168
| FIR-Aging Inspection | 7/11/2003 | 7/11/2003 | 7/11/2003 12:00:00 AM | | FAIL |
|
|
I spoke with Greg Johnson with Treasure Valley Fire and he said he would follow up on this project 7/11/2003 3:09:56 PM
|
BLD03-00117
| FIRE-Final Inspection | 7/10/2003 | 7/11/2003 | 7/11/2003 12:00:00 AM | A | PASS |
|
|
fire life safety finaled. Door hardware may be an issue. Structural inspector to verify 7/11/2003 1:07:00 PM
|
MIS03-00135
| FIR-Final | 7/10/2003 | 7/11/2003 | 7/11/2003 12:00:00 AM | A | FAIL |
|
|
fire doors catch on the carpet when closing on both the first and second floors, lower fire extinguishers to 48" on both floors, repair the emergency light on the first floor, repair the exit sign on the second floor 7/11/2003 10:47:20 AM
|
MIS03-00134
| FIR-Final | 7/10/2003 | 7/11/2003 | 7/11/2003 12:00:00 AM | A | FAIL |
|
|
fire doors catch on the carpet when closing on both the first and second floors, lower fire extinguishers to 48" on both floors, repair the emergency light on the first floor, repair the exit sign on the second floor 7/11/2003 10:47:32 AM
|
FIR03-00057
| INSP-Sprinkler Rough-in/Hydro | 7/10/2003 | 7/11/2003 | 7/11/2003 12:00:00 AM | P | FAIL |
|
|
provide approved review comments, provide signage on the the fire alarm/fire sprinkler room door, heat detector exceeds 24" from the sprinkler head in the elev. mach. room, provide access to the fire smoke damper, provide control for the fire smoke dampers per IBC 715.3.2.1, provide point descriptions for the fire alarm devices, elevator was locked out. Only the above items have been looked at. No other items inspected or tested. 7/11/2003 3:25:01 PM
|
BLD03-01654
| FIRE-Conference | 7/11/2003 | 7/11/2003 | 7/11/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 7/11/2003 at 8:42:46 AM. Contact: ###-####.
|